ErrorCode
Parameter
HSCSTS.ErrorCode
Displays the error codes detected by the HSC sub-system.
Error code sub-element
HSC counting error
code
Bit 15-8 (high byte)
Bit 7-0 (low byte)
Accumulator
Parameter
HSCApp.Accumulator
Sets the initial accumulator value when the High-Speed Counter starts. When the
HSC is in Counting mode, the Accumulator is automatically updated by the HSC
sub-system to reflect the actual HSC accumulator value.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Data type
BOOL
Error description
0-255
The non-zero value for the high byte indicates that the HSC error is due to the PLS data
setting. The value of the high byte indicates which element of the PLS data triggers the
error.
0x00
No error occurring.
0x01
Invalid HSC counting mode.
0x02
Invalid high preset.
0x03
Invalid overflow.
0x04
Invalid underflow.
0x05
No PLS data.
Data type
DINT
High-Speed Counter (HSC) instructions
HSC mode
User program access
0...9
read only
User program access
read/write
Chapter 14
327