Chapter 9
Communication instructions
ErrorID
code
69
208
209
210
217
218
222
224
255
Parameter
Path
CipConnMode
UcmmTimeout
180
SubErrorID
Error code description
115
Message timed out while waiting for a response from the link layer.
Server response format related error codes
65
Message reply does not match request.
68
Message reply data type not valid/supported. (MSG_CIPSYMBOLIC).
No IP address configured for the network.
Maximum number of connections used – no connections available.
Invalid internet address or node address.
Message execution was canceled by user. (Cancel parameter was set to TRUE).
No network buffer space available.
Reserved.
CIP response error code. SubErrorID specifies the CIP status and ExtErrorID specifies the CIP extended status value. Refer to the CIP
specification for possible error code values.
Channel is shutdown or reconfiguration is in progress. Error code occurs immediately after power on until a connection is established, and is
normal behavior.
It may also occur in one of the following situations:
• An Ethernet cable is disconnected
• An IP address cannot be detected
• A serial port plugin is present but not configured

CIPTARGETCFG data type

The following table describes the CIPTARGETCFG data type.
Data type
Description
STRING[80]
Path for the target. A maximum of two hops can be specified. The path syntax is:
• {"<port>,<node/slot address>"}2
See also
Target path for CIP messaging
USINT
CIP Connection type.
• 0 - Unconnected (default)
• 1 - Class3 connection
See also
CIP/EIP message connections
UDINT
Unconnected message timeout (in milliseconds). The amount of time to wait for a reply for unconnected
messages, including connection establishment for connected message.
• Valid values: 250-10,000.
• Set to 0 to use the default value of 3000.
• A value set to less than 250 will be set to 250 (minimum).
• A value set to greater than 10,000 will be set to 10,000 (maximum).
See also
CIP message timeout timers
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015