Chapter 14
High-Speed Counter (HSC) instructions
328
HP
Parameter
HSCSTS.HP
The HSCSTS.HP is the upper setpoint (in counts) that defines when the HSC
sub-system generates an interrupt.
The data loaded into the high preset must be less than or equal to the data resident
in the overflow (HSCAPP.OFSetting) parameter or an HSC error is generated.
This is the latest high preset setting, which may be updated by PLS function from
the PLS data block.
LP
Parameter
HSCSTS.LP
The HSCSTS.LP is the lower setpoint (in counts) that defines when the HSC
sub-system generates an interrupt.
The data loaded into the low preset must be greater than or equal to the data
resident in the underflow (HSCAPP.UFSetting) parameter or an HSC error is
generated. If the underflow and low preset values are negative numbers, the low
preset must be a number with a smaller absolute value.
This is the latest low preset setting, which may be updated by PLS function from
the PLS data block.
HPOutput
Parameter
HSCApp.HPOutput
Defines the state (1 = ON or 0 = OFF) of the outputs on the controller when the
high preset is reached. For more information on how to directly turn outputs on
or off based on the high preset, see OutputMask.
You can configure the high output bit pattern during initial setup, or you can use
the HSC function block to load the new parameters while the controller is
operating.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Data type
User program access
DINT
read only
Data type
HSC mode
DINT
Data type
User program access
UDINT
read/write
User program access
read only