Allen-Bradley PowerFlex 40 - Adjustable Frequency AC Drive Quick Start Guide

Also See for PowerFlex 40:

Advertisement

Allen-Bradley PowerFlex 40 - Adjustable Frequency AC Drive Quick Start Guide

Mounting Considerations

  • Mount the drive upright on a flat, vertical and level surface.
    Frame Screw Size Screw Torque DIN Rail
    B M4 (#8-32) 1.56-1.96 N-m (14-17 lb.-in.) 35 mm
    C M5 (#10-24) 2.45-2.94 N-m (22-26 lb.-in.)
    B (IP66, Type 4X) M6 (#12-24) 3.95-4.75 N-m (35-42 lb.-in.)
  • Protect the cooling fan by avoiding dust or metallic particles.
  • Do not expose to a corrosive atmosphere.
  • Protect from moisture and direct sunlight.

Minimum Mounting Clearances

See Drive Dimensions for mounting dimensions.
Minimum Mounting Clearances

Ambient Operating Temperatures

Ambient Temperature Enclosure Rating Minimum Mounting Clearances
Minimum Maximum
-10°C (14°F) 40°C (104°F) IP20, NEMA/UL Type Open Use Mounting Option A
IP66, NEMA/UL Type 4X Use Mounting Option A
IP30, NEMA/UL Type 1(1) Use Mounting Option B
50°C (122°F) IP20, NEMA/UL Type Open Use Mounting Option B
  1. Rating requires installation of the PowerFlex 40 IP 30, NEMA/UL Type 1 option kit.

Typical Grounding

Typical Grounding

Disconnecting MOVs

To prevent drive damage, the MOVs connected to ground shall be disconnected if the drive is installed on an ungrounded distribution system where the line-to-ground voltages on any phase could exceed 125% of the nominal line-to-line voltage. To disconnect these devices, remove the jumper shown in the figures below.

  1. Turn the screw counterclockwise to loosen.
  2. Pull the jumper completely out of the drive chassis.
  3. Tighten the screw to keep it in place.

Jumper Location
Jumper Location


Tighten screw after jumper removal.

Phase to Ground MOV Removal
Phase to Ground MOV Removal

Specifications, Fuses and Circuit Breakers

Drive Ratings

Output Ratings Input Ratings Branch Circuit Protection Power Dissipation
Catalog Number (1) kW (HP) Amps Voltage Range kVA Amps Fuses 140M Motor Protectors(3)(4) Contractors Min. Enclosure Volume(5) (in.3) IP20 Open Watts
100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output
22B-V2P3x104 0.4 (0.5) 2.3 90-132 1.15 9.0 15 140M-C2E-C16 100-C12 1655 40
22B-V5P0x104 0.75 (1.0) 5.0 90-132 2.45 20.3 35 140M-D8E-C20 100-C23 1655 60
22B-V6P0x104 1.1 (1.5) 6.0 90-132 3.0 24.0 40 140M-F8E-C32 100-C37 1655 80
200 - 240V AC (±10%) – 1-Phase(2) Input, 0 - 230V 3-Phase Output
22B-A2P3x104 0.4 (0.5) 2.3 180-264 1.15 6.0 10 140M-C2E-B63 100-C09 1655 40
22B-A5P0x104 0.75 (1.0) 5.0 180-264 2.45 12.0 20 140M-C2E-C16 100-C12 1655 60
22B-A8P0x104 1.5 (2.0) 8.0 180-264 4.0 18.0 30 140M-D8E-C20 100-C23 1655 85
22B-A012x104 2.2 (3.0) 12.0 180-264 5.5 25.0 40 140M-F8E-C32 100-C37 2069 125
200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output
22B-B2P3x104 0.4 (0.5) 2.3 180-264 1.15 2.5 6 140M-C2E-B40 100-C07 1655 40
22B-B5P0x104 0.75 (1.0) 5.0 180-264 2.45 5.7 10 140M-C2E-C10 100-C09 1655 60
22B-B8P0x104 1.5 (2.0) 8.0 180-264 4.0 9.5 15 140M-C2E-C16 100-C12 1655 85
22B-B012x104 2.2 (3.0) 12.0 180-264 5.5 15.5 25 140M-C2E-C16 100-C23 1655 125
22B-B017x104 3.7 (5.0) 17.5 180-264 8.6 21.0 30 140M-F8E-C25 100-C23 1655 180
22B-B024x104 5.5 (7.5) 24.0 180-264 11.8 26.1 40 140M-F8E-C32 100-C37 2069 235
22B-B033x104 7.5 (10.0) 33.0 180-264 16.3 34.6 60 140M-G8E-C45 100-C60 2069 305
380 - 480V AC (±10%) – 3-Phase Input, 0 - 460V 3-Phase Output
22B-D1P4x104 0.4 (0.5) 1.4 342-528 1.4 1.8 3 140M-C2E-B25 100-C07 1655 35
22B-D2P3x104 0.75 (1.0) 2.3 342-528 2.3 3.2 6 140M-C2E-B40 100-C07 1655 50
22B-D4P0x104 1.5 (2.0) 4.0 342-528 4.0 5.7 10 140M-C2E-B63 100-C09 1655 70
22B-D6P0x104 2.2 (3.0) 6.0 342-528 5.9 7.5 15 140M-C2E-C10 100-C09 1655 100
22B-D010x104 4.0 (5.0) 10.5 342-528 10.3 13.0 20 140M-C2E-C16 100-C23 1655 160
22B-D012x104 5.5 (7.5) 12.0 342-528 11.8 14.2 25 140M-D8E-C20 100-C23 2069 175
22B-D017x104 7.5 (10.0) 17.0 342-528 16.8 18.4 30 140M-D8E-C20 100-C23 2069 210
22B-D024x104 11.0 (15.0) 24.0 342-528 23.4 26.0 50 140M-F8E-C32 100-C43 2069 300
460 - 600V AC (±10%) – 3-Phase Input, 0 - 575V 3-Phase Output
22B-E1P7x104 0.75 (1.0) 1.7 414-660 2.1 2.3 6 140M-C2E-B25 100-C09 1655 50
22B-E3P0x104 1.5 (2.0) 3.0 414-660 3.65 3.8 6 140M-C2E-B40 100-C09 1655 70
22B-E4P2x104 2.2 (3.0) 4.2 414-660 5.2 5.3 10 140M-D8E-B63 100-C09 1655 100
22B-E6P6x104 4.0 (5.0) 6.6 414-660 8.1 8.3 15 140M-D8E-C10 100-C09 1655 160
22B-E9P9x104 5.5 (7.5) 9.9 414-660 12.1 11.2 20 140M-D8E-C16 100-C16 2069 175
22B-E012x104 7.5 (10.0) 12.2 414-660 14.9 13.7 25 140M-D8E-C16 100-C23 2069 210
22B-E019x104 11.0 (15.0) 19.0 414-660 23.1 24.1 40 140M-F8E-C25 100-C30 2069 300
  1. In the Catalog Numbers listed "x" represents enclosure type. Specifications are valid for all enclosure types. IP66, NEMA/UL Type 4X drive ratings are only available as Frame B drives.
  2. 200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114. Filter option is not available for IP66, NEMA/UL Type 4X rated drives.
  3. The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
  4. Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
  5. When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure.

Input/Output Ratings
Output Frequency: 0-400 Hz (Programmable)
Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6mA)

  • SRC (Source) Mode:
    18-24V = ON
    0-6V = OFF
  • SNK (Sink) Mode:
    0-6V = ON
    18-24V = OFF

Analog Control Inputs
4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum

Control Output

Programmable Output (form C relay) Opto Outputs Analog Outputs (10 bit)
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC 30V DC, 50mA 0-10V, 1k ohm Min.
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC Non-inductive 4-20mA, 525 ohm Max.

Fuses and Circuit Breakers
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Recommended Circuit Breakers: HMCP circuit breakers or equivalent.

Protective Features

  • Motor Protection: I2t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
  • Overcurrent: 200% hardware limit, 300% instantaneous fault
  • Over Voltage:
    100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
    200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
    380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
    460-600V AC Input – Trip occurs at 1005V DC bus voltage (equivalent to 711V AC incoming line)
  • Under Voltage:
    100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
    200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
    380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
    460-600V AC Input
    • If P042 = 3 "High Voltage" trip occurs at 487V DC bus voltage (344V AC incoming line);
    • If P042 = 2 "Low Voltage" trip occurs at 390V DC bus voltage (275V AC incoming line)
  • Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
  • Faultless Power Ride Through: 100 milliseconds

Dynamic Braking
Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 40 User Manual for DB resistor ordering information.

Power Wiring

Power Wire Rating Recommended Copper Wire
Unshielded 600V, 75°C (167°F) THHN/THWN 15 Mils insulated, dry location
Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2 Anixter OLF-7xxxxx, Belden 29501-29507 or equivalent
Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2 Anixter 7V-7xxxx-3G Shawflex 2ACD/3ACD or equivalent

Power Terminal Block
Power Terminal Block

Terminal(1) Description
R/L1, S/L2 1-Phase Input
R/L1, S/L2, T/L3 3-Phase Input
U/T1 To Motor U/T1 = Switch any two motor leads to change forward direction.
V/T2 To Motor V/T2
W/T3 To Motor W/T3
P2, P1 DC Bus Inductor Connection (C Frame drives only.)
The C Frame drive is shipped with a jumper between Terminals P2 and P1. Remove this jumper only when a DC Bus Inductor will be connected. Drive will not power up without a jumper or inductor connected.
DC+, DC- DC Bus Connection
BR+, BR- Dynamic Brake Resistor Connection
Safety Ground - PE

  1. Terminal screws may become loose during shipment. Ensure that all terminal screws are tightened to the recommended torque before applying power to the drive.

Power Terminal Block Specifications

Frame Maximum Wire Size(2) Minimum Wire Size(2) Torque
B 5.3 mm2 (10 AWG) 1.3 mm2 (16 AWG) 1.7-2.2 N-m (16-19 lb.-in.)
C 8.4 mm2 (8 AWG) 1.3 mm2 (16 AWG) 2.9-3.7 N-m (26-33 lb.-in.)
  1. Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Input Power Conditions

Input Power Condition Corrective Action
Low Line Impedance (less than 1% line reactance)
  • Install Line Reactor(2)
  • or Isolation Transformer
  • or Bus Inductor – 5.5-11 kW (7.5-15 HP) drives only
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
  • Install Line Reactor
  • or Isolation Transformer
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line to line voltage
  • Remove MOV jumper to ground.
  • or Install Isolation Transformer with grounded secondary if necessary.
Ungrounded distribution system
240V open delta configuration (stinger leg)(1)
  • Install Line Reactor
  1. For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in the middle to the neutral or earth is referred to as the "stinger leg," "high leg," "red leg," etc. This leg should be identified throughout the system with red or orange tape on the wire at each connection point. The stinger leg should be connected to the center Phase B on the reactor.
  2. Refer to Appendix B of the PowerFlex 40 User Manual for accessory ordering information.

I/O Wiring Recommendations(3)

Wire Type(s)(4) Description Minimum Insulation Rating
Belden 8760/9460
(or equiv.)
0.8 mm2 (18AWG), twisted pair, 100% shield with drain. 300V
60 degrees C
(140 degrees F)
Belden 8770
(or equiv.)
0.8 mm2 (18AWG), 3 conductor, shielded for remote pot only.
  1. If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
  2. Stranded or solid wire.

I/O Terminal Block Specifications

Frame Maximum Wire Size(5) Minimum Wire Size(5) Torque
B & C 1.3 mm2 (16 AWG) 0.2 mm2 (24 AWG) 0.5-0.8 N-m (4.4-7 lb.-in.)
  1. Maximum / minimum that the terminal block will accept - these are not recommendations.

Control Terminal Block

Control Wiring Block Diagram
Control Wiring Block Diagram

30V DC 125V AC 240V AC
Resistive 3.0A 3.0A 3.0A
Inductive 0.5A 0.5A 0.5A

  1. I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set to "3-Wire" or "Momt FWD/REV" control. In three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode]. All other stop sources are controlled by P037 [Stop Mode].
    P036 [Start Source] Stop I/O Terminal 01 Stop
    Keypad Per P037 Coast
    3-Wire Per P037 Per P037
    2-Wire Per P037 Coast
    RS485 Port Per P037 Coast


The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O Terminal 01 as a stop or enable input.

  1. Two wire control shown. For three wire control use a momentary input on I/O Terminal 02 to command a start. Use a maintained input for I/O Terminal 03 to change direction.
  2. When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as shown, to prevent damage to the output.
  3. When the ENBL jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing a coast to stop without software interpretation.

Control I/O Terminal Designations

No. Signal Default Description Param.
R1 Relay N.O. Fault Normally open contact for output relay. A055
R2 Relay Common Common for output relay.
R3 Relay N.C. Fault Normally closed contact for output relay. A055
Analog Output Select DIP Switch 0-10V Sets analog output to either voltage or current. Setting must match A065 [Analog Out Sel].
Sink/Source DIP Switch Source (SRC) Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.
01 Stop(1) Coast The factory installed jumper or a normally closed input must be present for the drive to start. P036(1)
02 Start/Run FWD Not Active Command comes from the integral keypad by default. To disable reverse operation, see A095 [Reverse Disable]. P036, P037
03 Direction/Run REV Not Active P036, P037, A095
04 Digital Common For digital inputs. Electronically isolated with digital inputs from analog I/O and opto outputs.
05 Digital Input 1 Preset Freq Program with A051 [Digital In1 Sel]. A051
06 Digital Input 2 Preset Freq Program with A052 [Digital In2 Sel]. A052
07 Digital Input 3 Local Program with A053 [Digital In3 Sel]. A053
08 Digital Input 4 Jog Forward Program with A054 [Digital In4 Sel]. A054
09 Opto Common For opto-coupled outputs. Electronically isolated with opto outputs from analog I/O and digital inputs.
11 +24V DC Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100mA.
12 +10V DC Referenced to Analog Common.
Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.
P038
13 ±10V In(2) Not Active For external 0-10V (unipolar) or ±10V (bipolar) input supply (input impedance = 100k ohm) or potentiometer wiper. P038, A051-A054, A123, A132
14 Analog Common For 0-10V In or 4-20mA In. Electronically isolated with analog inputs and outputs from digital I/O and opto outputs.
15 4-20mA In(2) Not Active For external 4-20mA input supply (input impedance = 250 ohm). P038, A051-A054, A132
16 Analog Output OutFreq 0-10 The default analog output is 0-10V. To covert to a current value, change the Analog Output Select DIP Switch to 0-20mA. Program with A065 [Analog Out Sel]. Max analog value can be scaled with A066 [Analog Out High].
Maximum Load:
4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
A065, A066
17 Opto Output 1 MotorRunning Program with A058 [Opto Out1 Sel] A058, A059, A064
18 Opto Output 2 At Frequency Program with A061 [Opto Out2 Sel] A061, A062, A064
19 RS485 (DSI) Shield Terminal should be connected to safety ground - PE when using the RS485 (DSI) communications port.
  1. See Footnotes 1 and 4 "Control Terminal Block" section.
  2. 0-10V In and 4-20mA In are distinct input channels and may be connected simultaneously. Inputs may be used independently for speed control or jointly when operating in PID mode.

Prepare For Drive Start-Up

shock hazard ATTENTION: Power must be applied to the drive to perform the following start-up procedures. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove All Power including user supplied control voltages. User supplied voltages may exist even when main AC power is not applied to the drive. Correct the malfunction before continuing.

Before Applying Power to the Drive

  1. Confirm that all inputs are connected to the correct terminals and are secure.
  2. Verify that AC line power at the disconnect device is within the rated value of the drive.
  3. Verify that any digital control power is 24 volts.
  4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to match your control wiring scheme. See "Control Terminal Block" for location.

    The default control scheme is Source (SRC). The Stop terminal is jumpered (I/O Terminals 01 and 11) to allow starting from the keypad. If the control scheme is changed to Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and installed between I/O Terminals 01 and 04.
  5. Verify that the Stop input is present or the drive will not start.

    If I/O Terminal 01 is used as a stop input, the jumper between I/O Terminals 01 and 11 must be removed.

Applying Power to the Drive

  1. Apply AC power and control voltages to the drive.
  2. Familiarize yourself with the integral keypad features before setting any Program Group parameters.

If a fault appears on power up, refer to "Fault Codes" for an explanation of the fault code.

Start, Stop, Direction and Speed Control

Factory default parameter values allow the drive to be controlled from the integral keypad. No programming is required to start, stop, change direction and control speed directly from the integral keypad.

To disable reverse operation, see A095 [Reverse Disable].

Changing the Speed Reference of an IP66, NEMA/UL Type 4X rated drive
When a Display Group parameter, for example, d001 [Output Freq] is displayed, and P038 [Speed Ref] is set to A069 [Internal Freq], you can change the internal frequency using the Up Arrow and Down Arrow keys.

When the internal frequency is being adjusted, its value is displayed and the Hertz LED flashes. Any changes are saved immediately. The display then returns to the Display Group parameter previously shown.
TIP: By default, the speed reference of an IP66, NEMA/UL Type 4X rated drive is set to the internal frequency, A069 [Internal Freq].
TIP: You can also change the speed reference by editing the parameter A069 [Internal Freq] in program mode. For details on how to enter the program mode, see the section, "Viewing and Editing Parameters."
The default value of A069 [Internal Freq] is 0 Hz. For IP20 rated PowerFlex 40 drives, the default value of this parameter is 60 Hz.

Integral Keypad

Menu Description
Display Group (View Only)
Consists of commonly viewed drive operating conditions.
Basic Program Group
Consists of most commonly used programmable functions.
Advanced Program Group
Consists of remaining programmable functions.
Fault Designator
Consists of list of codes for specific fault conditions. Displayed only when fault is present.

Integral Keypad Overview

No. LED LED State Description
Run/Direction Status Steady Red Indicates drive is running and commanded motor direction.
Flashing Red Drive has been commanded to change direction. Indicates actual motor direction while decelerating to zero.
Alphanumeric Display Steady Red Indicates parameter number, parameter value, or fault code.
Flashing Red Single digit flashing indicates that digit can be edited.
All digits flashing indicates a fault condition.
Displayed Units Steady Red Indicates the units of the parameter value being displayed.
Program Status Steady Red Indicates parameter value can be changed.
Fault Status Flashing Red Indicates drive is faulted.
Pot Status Steady Green Indicates potentiometer on Integral Keypad is active.(1)
Start Key Status Steady Green Indicates Start key on Integral Keypad is active.
The Reverse key is also active unless disabled by A095 [Reverse Disable].
No. Key Name Description
Escape Back one step in programming menu.
Cancel a change to a parameter value and exit Program Mode.
Select Advance one step in programming menu.
Select a digit when viewing parameter value.
Up Arrow Down Arrow Scroll through groups and parameters.
Increase/decrease the value of a flashing digit.
Used to adjust internal frequency of IP66, NEMA/UL Type 4X rated drives only when a Display Group parameter is shown and P038 [Speed Reference] is set to internal frequency, A069 [Internal Freq].
Enter Advance one step in programming menu.
Save a change to a parameter value.
Potentiometer(1) Used to control speed of drive. Default is active.
Controlled by parameter P038 [Speed Reference].
Start Used to start the drive. Default is active.
Controlled by parameter P036 [Start Source].
Reverse Used to reverse direction of the drive. Default is active.
Controlled by parameters P036 [Start Source] and A095 [Reverse Disable].
Stop Used to stop the drive or clear a fault.
This key is always active.
Controlled by parameter P037 [Stop Mode].
  1. IP66, NEMA/UL Type 4X rated drives are not equipped with a potentiometer.

Viewing and Editing Parameters

The last user-selected Display Group parameter is saved when power is removed and is displayed by default when power is reapplied.
The following is an example of basic integral keypad and display functions. This example provides basic navigation instructions and illustrates how to program the first Program Group parameter.

Step Key(s) Example Displays
1 When power is applied, the last user-selected Display Group parameter number is briefly displayed with flashing characters. The display then defaults to that parameter's current value. (Example shows the value of d001 [Output Freq] with the drive stopped.)
2 Press Esc once to display the Display Group parameter number shown on power-up. The parameter number will flash.
3 Press Esc again to enter the group menu. The group menu letter will flash.
4 Press the Up Arrow or Down Arrow to scroll through the group menu (d, P and A).
5 Press Enter or Sel to enter a group. The right digit of the last viewed parameter in that group will flash.
6 Press the Up Arrow or Down Arrow to scroll through the parameters that are in the group.
7 Press Enter or Sel to view the value of aparameter. If you do not want to edit the value, press Esc to return to the parameter number.
8 Press Enter or Sel to enter program mode to edit the parameter value. The right digit will flash and the Program LED will illuminate if the parameter can be edited.
9 Press the Up Arrow or Down Arrow to change the parameter value. If desired, press Sel to move from digit to digit or bit to bit. The digit or bit that you can change will flash.
10 Press Esc to cancel a change. The digit will stop flashing, the previous value is restored and the Program LED will turn off.
Or
Press Enter to save a change. The digit will stop flashing and the Program LED will turn off.
11 Press Esc to return to the parameter list. Continue to press Esc to back out of the programming menu.
If pressing Esc does not change the display, then d001 [Output Frequency] is displayed. Press Enter or Sel to enter the group menu.

The Basic Program Group contains the most commonly changed parameters.

Display Group Parameters

No. Parameter Min/Max Display/Options
d001 [Output Freq] 0.0/[Maximum Freq] 0.1 Hz
d002 [Commanded Freq] 0.0/[Maximum Freq] 0.1 Hz
d003 [Output Current] 0.00/(Drive Amps × 2) 0.01 Amps
d004 [Output Voltage] 0/Drive Rated Volts 1 VAC
d005 [DC Bus Voltage] Based on Drive Rating 1 VDC
d006 [Drive Status] 0/1 (1 = Condition True) Bit 3
Decelerating
Bit 2
Accelerating
Bit 1
Forward
Bit 0
Running
d007d009 [Fault x Code] F2/F122 F1
d010 [Process Display] 0.00/9999 0.01 – 1
d012 [Control Source] 0/9 Digit 1 = Speed Command
(See P038; 9 = "Jog Freq")
Digit 0 = Start Command
(See P036; 9 = "Jog")
d013 [Contrl In Status] 0/1 (1 = Input Present) Bit 3
DB Trans On
Bit 2
Stop Input
Bit 1
Dir/REV Inv
Bit 0
Start/FWD In
d014 [Dig In Status] 0/1 (1 = Input Present) Bit 3
Digital In 4
Bit 2
Digital In 3
Bit 1
Digital In 2
Bit 0
Digital In 1
d015 [Comm Status] 0/1 (1 = Condition True) Bit 3
Comm Error
Bit 2
DSI Option
Bit 1
Transmitting
Bit 0
Receiving
d016 [Control SW Ver] 1.00/99.99 0.01
d017 [Drive Type] 1001/9999 1
d018 [Elapsed Run Time] 0/9999 Hrs 1 = 10 Hrs
d019 [Testpoint Data] 0/FFFF 1 Hex
d020 [Analog In 0-10V] 0.0/100.0% 0.1%
d021 [Analog In 4-20mA] 0.0/100.0% 0.1%
d022 [Output Power] 0.00/(Drive Power × 2) 0.01 kW
d023 [Output Powr Fctr] 0.0/180.0 deg 0.1 deg
d024 [Drive Temp] 0/120 degC 1 degC
d025 [Counter Status] 0/9999 1
d026 [Timer Status] 0.0/9999 Secs 0.1 Secs
d028 [Stp Logic Status] 0/7 1
d029 [Torque Current] 0.00/(Drive Amps × 2) 0.01 Amps

Smart Start-Up with Basic Program Group Parameters

The PowerFlex 40 is designed so that start up is simple and efficient. The Program Group contains the most commonly used parameters.
= Stop drive before changing this parameter.

No. Parameter Min/Max Display/Options Default
P031
[Motor NP Volts] 20/Drive Rated Volts 1 VAC
Based on Drive Rating
Set to the motor nameplate rated volts.
P032
[Motor NP Hertz] 15/400 Hz 1 Hz
60 Hz
Set to the motor nameplate rated frequency.
P033
[Motor OL Current] 0.0/(Drive Rated Amps×2) 0.1 Amps
Based on Drive Rating
Set to the maximum allowable motor current.
P034
[Minimum Freq] 0.0/400.0 Hz 0.1 Hz
0.0 Hz
Sets the lowest frequency the drive will output continuously.
P035
[Maximum Freq] 0/400 Hz 1 Hz
60 Hz
Sets the highest frequency the drive will output.
P036
[Start Source] 0/6 0 = "Keypad"(1)
1 = "3-Wire"
2 = "2-Wire"
3 = "2-W Lvl Sens"
4 = "2-W Hi Speed"
5 = "Comm Port"
6 = "Momt FWD/REV"
0
Sets the control scheme used to start the drive.
  1. When active, the Reverse key is also active unless disabled by A095 [Reverse Disable].
P037
[Stop Mode] 0/9 0 = "Ramp, CF"(1)
1 = "Coast, CF"(1)
2 = "DC Brake, CF"(1)
3 = "DCBrkAuto, CF"(1)
4 = "Ramp"
5 = "Coast"
6 = "DC Brake"
7 = "DC BrakeAuto"
8 = "Ramp+EM B,CF"
9 = "Ramp+EM Brk"
  1. Stop input also clears active fault.
0
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O Terminal 03), RS485 port] except as noted below.

I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set for "3-Wire" control. When in three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode].
P038
[Speed Reference] 0/7 0 = "Drive Pot"
1 = "InternalFreq"
2 = "0-10V Input"
3 = "4-20mA Input"
4 = "Preset Freq"
5 = "Comm Port"
6 = "Stp Logic"
7 = "Anlg In Mult"
0
1 (IP66, Type 4X)
Sets the source of the speed reference to the drive.

When A051 or A052 [Digital Inx Sel] is set to option 2, 4, 5, 6, 13 or 14 and the digital input is active, A051, A052, A053 or A054 will override the speed reference commanded by this parameter.
P039
[Accel Time 1] 0.0/600.0 Secs 0.1 Secs
10.0 Secs
Sets the rate of accel for all speed increases.
P040
[Decel Time 1] 0.1/600.0 Secs 0.1 Secs
10.0 Secs
Sets the rate of decel for all speed decreases.
P041
[Reset To Defalts] 0/1 0 = "Ready/Idle"
1 = "Factory Rset"
0
Resets all parameter values to factory defaults.
P042
[Voltage Class] 2/3 2 = "Low Voltage" (480V)
3 = "High Voltage" (600V)
3
Sets the voltage class of 600V drives.
P043
[Motor OL Ret] 0/1 0 = "Disabled"
1 = "Enabled"
0
Enables/disables the Motor Overload Retention function.

Advanced Group Parameters

No. Parameter Min/Max Display/Options Default
A051 A052 A053 A054
[Digital In1 Sel] I/O Terminal 05 [Digital In2 Sel] I/O Terminal 06 [Digital In3 Sel] I/O Terminal 07 [Digital In4 Sel] I/O Terminal 08 0/27 0 = "Not Used"
1 = "Acc & Dec 2"
2 = "Jog"
3 = "Aux Fault"
4 = "Preset Freq"
5 = "Local"(1)
6 = "Comm Port"
7 = "Clear Fault"
8 = "RampStop, CF"
9 = "CoastStop, CF"
10 = "DCInjStop, CF"
11 = "Jog Forward"
12 = "Jog Reverse"
13 = "10V In Ctrl"
14 = "20mA In Ctrl"
15 = "PID Disable"
16 = "MOP Up"
17 = "MOP Down"
18 = "Timer Start"
19 = "Counter In"
20 = "Reset Timer"
21 = "Reset Countr"
22 = "Rset Tim&Cnt"
23 = "Logic In1"
24 = "Logic In2"
25 = "Current Lmt2"
26 = "Anlg Invert"
27 = "EM Brk Rlse"
4
4
5
11

  1. Speed source for IP66, NEMA/ UL Type 4X rated drives comes from A069 [Internal Freq].
A055 [Relay Out Sel] 0/24 0 = "Ready/Fault"
1 = "At Frequency"
2 = "MotorRunning"
3 = "Reverse"
4 = "Motor Overld"
5 = "Ramp Reg"
6 = "Above Freq"
7 = "Above Cur"
8 = "Above DCVolt"
9 = "Retries Exst"
10 = "Above Anlg V"
11 = "Logic In 1"
12 = "Logic In 2"
13 = "Logic 1 & 2"
14 = "Logic 1 or 2"
15 = "StpLogic Out"
16 = "Timer Out"
17 = "Counter Out"
18 = "Above PF Ang"
19 = "Anlg In Loss"
20 = "ParamControl"
21 = "NonRec Fault"
22 = "EM Brk Cntrl"
23 = "Above Fcmd"
24 = "MsgControl" (for FRN 6.01 and later)
0
A056 [Relay Out Level] 0.0/9999 0.1 0.0
A058 A061 [Opto Out1 Sel]
[Opto Out2 Sel]
0/24 See A055 for Options. 2
1
A059 A062 [Opto Out1 Level]
[Opto Out2 Level]
0.0/9999 0.1 0.0
A055, A058 & A061 Setting A056, A059 & A062 Min/Max
6 0/400 Hz
7 0/180%
8 0/815 Volts
10 0/100%
16 0.1/9999 Secs
17 1/9999 Counts
18 1/180 degs
20 0/1
23 0/400 Hz
A064 [Opto Out Logic] 0/3 1 0
A064 Option Opto Out1 Logic Opto Out2 Logic
0 NO (Normally Open) NO (Normally Open)
1 NC (Normally Closed) NO (Normally Open)
2 NO (Normally Open) NC (Normally Closed)
3 NC (Normally Closed) NC (Normally Closed)
A065 [Analog Out Sel] 0/23 1 0
Option Output Range Minimum Output Value Maximum Output Value [Analog Out High] DIP Switch Position
0 "OutFreq 0-10" 0-10V 0V = 0 Hz P035 [Maximum Freq] 0-10V
1 "OutCurr 0-10" 0-10V 0V = 0 Amps 200% Drive Rated FLA 0-10V
2 "OutVolt 0-10" 0-10V 0V = 0 Volts 120% Drive Rated Output Volts 0-10V
3 "OutPowr 0-10" 0-10V 0V = 0 kW 200% Drive Rated Power 0-10V
4 "TstData 0-10" 0-10V 0V = 0000 65535 (Hex FFFF) 0-10V
5 "OutFreq 0-20" 0-20 mA 0 mA = 0 Hz P035 [Maximum Freq] 0-20 mA
6 "OutCurr 0-20" 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
7 "OutVolt 0-20" 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output Volts 0-20 mA
8 "OutPowr 0-20" 0-20 mA 0 mA = 0 kW 200% Drive Rated Power 0-20 mA
9 "TstData 0-20" 0-20 mA 0 mA = 0000 65535 (Hex FFFF) 0-20 mA
10 "OutFreq 4-20" 4-20 mA 4 mA = 0 Hz P035 [Maximum Freq] 0-20 mA
11 "OutCurr 4-20" 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
12 "OutVolt 4-20" 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output Volts 0-20 mA
13 "OutPowr 4-20" 4-20 mA 4 mA = 0 kW 200% Drive Rated Power 0-20 mA
14 "TstData 4-20" 4-20 mA 4 mA = 0000 65535 (Hex FFFF) 0-20 mA
15 "OutTorq 0-10" 0-10V 0V = 0 Amps 200% Drive Rated FLA 0-10V
16 "OutTorq 0-20" 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
17 "OutTorq 4-20" 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
18 "Setpnt 0-10" 0-10V 0V = 0% 100.0% Setpoint Setting 0-10V
19 "Setpnt 0-20" 0-20 mA 0 mA = 0% 100.0% Setpoint Setting 0-20 mA
20 "Setpnt 4-20" 4-20 mA 4 mA = 0% 100.0% Setpoint Setting 0-20 mA
21 "MinFreq 0-10" 0-10V 0V = Min. Freq P035 [Maximum Freq] 0-10V
22 "MinFreq 0-20" 0-20 mA 0 mA = Min. Freq P035 [Maximum Freq] 0-20 mA
23 "MinFreq 4-20" 4-20 mA 4 mA = Min. Freq P035 [Maximum Freq] 0-20 mA
A066 [Analog Out High] 0/800% 1% 100%
A067 [Accel Time 2] 0.0/600.0 Secs 0.1 Secs 20.0 Secs
A068 [Decel Time 2] 0.1/600.0 Secs 0.1 Secs 20.0 Secs
A069 [Internal Freq] 0.0/400.0 Hz 0.1 Hz 0.0 Hz (for IP66, NEMA/UL Type 4X drives)
60.0 Hz (for IP20 drives)
A070
A071
A072
A073
A074
A075
A076
A077
[Preset Freq 0](1)
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
[Preset Freq 4]
[Preset Freq 5]
[Preset Freq 6]
[Preset Freq 7]
0.0/400.0 Hz 0.1 Hz 0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
  1. To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.
Input State of Digital In 1
(I/O Terminal 05)
Input State of Digital In 2
(I/O Terminal 06)
Input State of Digital In 3
(I/O Terminal 07)
Frequency Source Accel / Decel Parameter Used(2)
0 0 0 [Preset Freq 0] [Accel Time 1] / [Decel Time 1]
1 0 0 [Preset Freq 1] [Accel Time 1] / [Decel Time 1]
0 1 0 [Preset Freq 2] [Accel Time 2] / [Decel Time 2]
1 1 0 [Preset Freq 3] [Accel Time 2] / [Decel Time 2]
0 0 1 [Preset Freq 4] [Accel Time 1] / [Decel Time 1]
1 0 1 [Preset Freq 5] [Accel Time 1] / [Decel Time 1]
0 1 1 [Preset Freq 6] [Accel Time 2] / [Decel Time 2]
1 1 1 [Preset Freq 7] [Accel Time 2] / [Decel Time 2]
  1. When a Digital Input is set to "Accel 2 & Decel 2", and the input is active, that input overrides the settings in this table.
A078 [Jog Frequency] 0.0/[Maximum Freq] 0.1 Hz 10.0 Hz
A079 [Jog Accel/Decel] 0.1/600.0 Secs 0.1 Secs 10.0 Secs
A080
[DC Brake Time] 0.0/99.9 Secs 0.1 Secs
0.0 Secs
A setting of 99.9 Secs = Continuous
A081 [DC Brake Level] 0.0/(Drive Amps × 1.8) 0.1 Amps Amps × 0.05
A082
[DB Resistor Sel] 0/99 0 = "Disabled"
1 = "Normal RA Res"
2 = "NoProtection"
3-99 = % of Duty Cycle
0
A083 [S Curve %] 0/100% 1% 0% (Disabled)
A084
[Boost Select] 0/14 Settings in % of base voltage.
0 = "Custom V/Hz"
Variable Torque
1 = "30.0, VT"
2 = "35.0, VT"
3 = "40.0, VT"
4 = "45.0, VT"
Constant Torque
5 = "0.0, no IR"
6 = "0.0"
7 = "2.5, CT"
8 = "5.0, CT"
9 = "7.5, CT"
10 = "10.0, CT"
11 = "12.5, CT"
12 = "15.0, CT"
13 = "17.5, CT"
14 = "20.0, CT"
8
7 4-11 kW (5-15 HP)
Only active when A125 [Torque Perf Mode] is set to 0 "V/Hz".
A085
[Start Boost] 0.0/25.0% 0.1% 2.5%
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A086
[Break Voltage] 0.0/100.0% 0.1% 25.0%
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A087
[Break Frequency] 0.0/400.0 Hz 0.1 Hz 15.0 Hz
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A088 [Maximum Voltage] 20/Rated Volts 1 VAC Rated Volts
A089 [Current Limit 1] 0.1/(Drive Amps × 1.8) 0.1 Amps Amps × 1.5
A090 [Motor OL Select] 0/2 0 = "No Derate"
1 = "Min Derate"
2 = "Max Derate"
0
A091 [PWM Frequency] 2.0/16.0 kHz 0.1 kHz 4.0 kHz
A092 [Auto Rstrt Tries] 0/9 1 0
A093 [Auto Rstrt Delay] 0.0/300.0 Secs 0.1 Secs 1.0 Secs
A094
[Start At PowerUp] 0/1 0 = "Disabled"
1 = "Enabled"
0
A095 [Reverse Disable] 0/1 0 = "Rev Enabled"
1 = "Rev Disabled"
0
A096 [Flying Start En] 0/1 0 = "Disabled"
1 = "Enabled"
0
A097 [Compensation] 0/3 0 = "Disabled"
1 = "Electrical"
2 = "Mechanical"
3 = "Both"
1
A098 [SW Current Trip] 0.0/(Drive Amps × 2) 0.1 Amps 0.0 (Disabled)
A099 [Process Factor] 0.1/999.9 0.1 30.0
A100
[Fault Clear] 0/2 0 = "Ready/Idle"
1 = "Reset Fault"
2 = "Clear Buffer"
0
A101 [Program Lock] 0/9999 0 = "Unlocked"
1 = "Locked"
0
A102 [Testpoint Sel] 400/FFFF 1 Hex 400
A103
[Comm Data Rate] 0/5 0 = "1200"
1 = "2400"
2 = "4800"
3 = "9600"
4 = "19.2K"
5 = "38.4K"
3
Power to drive must be cycled before any changes will affect drive operation.
A104
[Comm Node Addr] 1/247 1
100
Power to drive must be cycled before any changes will affect drive operation.
A105 [Comm Loss Action] 0/3 0 = "Fault"
1 = "Coast Stop"
2 = "Stop"
3 = "Continu Last"
0
A106 [Comm Loss Time] 0.1/60.0 Secs 0.1 Secs 5.0 Secs
A107
[Comm Format] 0/5 0 = "RTU 8-N-1"
1 = "RTU 8-E-1"
2 = "RTU 8-O-1"
3 = "RTU 8-N-2"
4 = "RTU 8-E-2"
5 = "RTU 8-O-2"
0
Power to drive must be cycled before any changes will affect drive operation.
A108 [Language] 1/10 1 = "English"
2 = "Français"
3 = "Español"
4 = "Italiano"
5 = "Deutsch"
6 = "Reserved"
7 = "Português"
8 = "Reserved"
9 = "Reserved"
10 = "Nederlands"
1
A109 [Anlg Out Setpt] 0.0/100.0% 0.1% 0.0%
A110
[Anlg In 0-10V Lo] 0.0/100.0% 0.1% 0.0%
A111
[Anlg In 0-10V Hi] 0.0/100.0% 0.1% 100.0%
A112
[Anlg In4-20mA Lo] 0.0/100.0% 0.1% 0.0%
A113
[Anlg In4-20mA Hi] 0.0/100.0% 0.1% 100.0%
A114 [Slip Hertz @ FLA] 0.0/10.0 Hz 0.1 Hz 2.0 Hz
A115 [Process Time Lo] 0.00/99.99 0.01 0.00
A116 [Process Time Hi] 0.00/99.99 0.01 0.00
A117 [Bus Reg Mode] 0/1 0 = "Disabled"
1 = "Enabled"
1
A118 [Current Limit 2] 0.1/(Drive Amps × 1.8) 0.1 Amps Amps × 1.5
A119 [Skip Frequency] 0/400 Hz 1 Hz 0 Hz
A120 [Skip Freq Band] 0.0/30.0 Hz 0.1 Hz 0.0 Hz
A121 [Stall Fault Time] 0/5 0 = "60 Seconds"
1 = "120 Seconds"
2 = "240 Seconds"
3 = "360 Seconds"
4 = "480 Seconds"
5 = "Flt Disabled"
0
A122 [Analog In Loss] 0/6 0 = "Disabled"
1 = "Fault (F29)"
2 = "Stop"
3 = "Zero Ref"
4 = "Min Freq Ref"
5 = "Max Freq Ref"
6 = "Int Freq Ref"
0
A123 [10V Bipolar Enbl] 0/1 0 = "Uni-Polar In"
1 = "Bi-Polar In"
0
A124
[Var PWM Disable] 0/1 0 = "Enabled"
1 = "Disabled"
0
A125
[Torque Perf Mode] 0/1 0 = "V/Hz"
1 = "Sensrls Vect"
1
A126 [Motor NP FLA] 0.1/(Drive Amps × 2) 0.1 Amps Rated Amps
A127 [Autotune] 0/2 0 = "Ready/Idle"
1 = "Static Tune"
2 = "Rotate Tune"
0
A128 [IR Voltage Drop] 0.0/230.0 VAC 0.1 VAC Rated Volts
A129 [Flux Current Ref] 0.00/[Motor NP FLA] 0.01 Amps Rated Amps
A130 [PID Trim Hi] 0.0/400.0 0.1 60.0
A131 [PID Trim Lo] 0.0/400.0 0.1 0.0
A132 [PID Ref Sel] 0/8 0 = "PID Disabled"
1 = "PID Setpoint"
2 = "0-10V Input"
3 = "4-20mA Input"
4 = "Comm Port"
5 = "Setpnt, Trim"
6 = "0-10V, Trim"
7 = "4-20mA, Trim"
8 = "Comm, Trim"
0
A133 [PID Feedback Sel] 0/2 0 = "0-10V Input"
1 = "4-20mA Input"
2 = "Comm Port"
0
A134 [PID Prop Gain] 0.00/99.99 0.01 0.01
A135 [PID Integ Time] 0.0/999.9 Secs 0.1 Secs 0.1 Secs
A136 [PID Diff Rate] 0.00/99.99 (1/Secs) 0.01 (1/Secs) 0.01 (1/Secs)
A137 [PID Setpoint] 0.0/100.0% 0.1% 0.0%
A138 [PID Deadband] 0.0/10.0% 0.1% 0.0%
A139 [PID Preload] 0.0/400.0 Hz 0.1 Hz 0.0 Hz
A140- A147 [Stp Logic 0-7] 0001/bAFF 4 Digits 00F1
A150- A157 [Stp Logic Time 0-7] 0.0/999.9 Secs 0.1 Secs 30.0 Secs
A160 [EM Brk Off Delay] 0.01/10.00 Secs 0.01 Secs 2.00 Secs
A161 [EM Brk On Delay] 0.01/10.00 Secs 0.01 Secs 2.00 Secs
A162 [MOP Reset Sel] 0/1 0 = "Zero MOP Ref"
1 = "Save MOP Ref"
1
A163 [DB Threshold] 0.0/110.0% 0.0% 100.0%
A164 [Comm Write Mode] 0/1 0 = "Save"
1 = "RAM Only"
0
A165 [Anlg Loss Delay] 0.0/20.0 Secs 0.1 Secs 0.0 Secs
A166 [Analog In Filter] 0/14 1 0
A167 [PID Invert Error] 0/1 0 = "Not Inverted"
1 = "Inverted"
0

Fault Codes

To clear a fault, press the Stop key, cycle power or set A100 [Fault Clear] to 1 or 2.

No. Fault Description
F2 Auxiliary Input(1) Check remote wiring.
F3 Excessive DC Bus voltage ripple Monitor the incoming line for phase loss or line imbalance. Then, check input line fuse.
F4 UnderVoltage(1) Monitor the incoming AC line for low voltage or line power interruption.
F5 OverVoltage(1) Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.
F6 Motor Stalled(1) Increase [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit].
F7 Motor Overload(1) An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current].
F8 Heatsink OvrTmp(1) Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded 40°C (104°F) for IP 30/NEMA 1/UL Type 1 installations or 50°C (122°F) for Open type installations. Check fan.
F12 HW OverCurrent Check programming. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess current.
F13 Ground Fault Check the motor and external wiring to the drive output terminals for a grounded condition.
F29 Analog Input Loss(1) An analog input is configured to fault on signal loss. A signal loss has occurred.
F33 Auto Rstrt Tries Correct the cause of the fault and manually clear.
F38 Phase U to Gnd Check the wiring between the drive and motor. Check motor for grounded phase. Replace drive if fault cannot be cleared.
F39 Phase V to Gnd
F40 Phase W to Gnd
F41 Phase UV Short Check the motor and drive output terminal wiring for a shorted condition. Replace drive if fault cannot be cleared.
F42 Phase UW Short
F43 Phase VW Short
F48 Params Defaulted The drive was commanded to write default values to EEPROM. Clear the fault or cycle power to the drive. Program the drive parameters as needed.
F63 SW OverCurrent(1) Check load requirements and A098 [SW Current Trip] setting.
F64 Drive Overload Reduce load or extend Accel Time.
F70 Power Unit Cycle power. Replace drive if fault cannot be cleared.
F71 Net Loss The communication network has faulted.
F80 SVC Autotune The autotune function was either cancelled by the user of failed.
F81 Comm Loss If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. Check connection. An adapter was intentionally disconnected. Turn off using A105 [Comm Loss Action].
F100 Parameter Checksum Restore factory defaults.
F122 I/O Board Fail Cycle power. Replace drive if fault cannot be cleared.
  1. Auto-Reset/Run type fault. Configure with parameters A092 and A093.

Drive Dimensions

PowerFlex 40 Frames – Ratings are in kW and (HP)

Frame 120V AC – 1-Phase 240V AC – 1-Phase 240V AC – 3-Phase 480V AC – 3-Phase 600V AC – 3-Phase
B 0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
C(1) 2.2 (3.0) 5.5 (7.5)
7.5 (10.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
  1. IP66, NEMA/UL Type 4X rated drives are not availble in Frame C drive ratings.

IP20, NEMA/UL Type Open
Drive Dimensions - Part 1

Dimensions are in millimeters and (inches).
Weights are in kilograms and (pounds).

Frame A B C D E F Ship Weight
B 100
(3.94)
180
(7.09)
136
(5.35)
87
(3.43)
168
(6.61)
87.4
(3.44)
2.2
(4.9)
C 130
(5.1)
260
(10.2)
180
(7.1)
116
(4.57)
246
(9.7)
4.3
(9.5)

Communication, RFI Filter, IP 30/NEMA 1/UL Type 1 Option Kits
Drive Dimensions - Part 2

Dimension Option B Frame Drive C Frame Drive
A Comm Cover 25 (0.98) 25 (0.98)
B EMC Line Filter 50 (1.97) 60 (2.36)
C EMC Line Filter 229 (9.02) 309 (12.17)
D IP30/NEMA 1/UL
Type 1
33 (1.30) 60 (2.36)
IP30/NEMA 1/UL
Type 1 for Comm Cover
64 (2.52) 60 (2.36)

IP66, NEMA Type/UL Type 4X – Dimensions are in millimeters and (inches) Weights are in kilograms and (pounds).
Drive Dimensions - Part 3
Weight
5.2 (11.5)

General Precautions

shock hazard ATTENTION: The drive contains high voltage capacitors which take time to discharge after removal of mains supply. Before working on drive, ensure isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death.
Darkened display LEDs is not an indication that capacitors have discharged to safe voltage levels.
caution ATTENTION: Equipment damage and/or personal injury may result if parameter A092 [Auto Rstrt Tries] or A094 [Start At PowerUp] is used in an inappropriate application. Do not use this function without considering applicable local, national and international codes, standards, regulations or industry guidelines.
caution ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.
caution ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, "Guarding Against Electrostatic Damage" or any other applicable ESD protection handbook.
caution ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.

Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
www.rockwellautomation.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Allen-Bradley PowerFlex 40 - Adjustable Frequency AC Drive Quick Start Guide

Advertisement

Need Assistance?

Do you have a question about the PowerFlex 40 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents