MSG_MODBUS Write variables
The following table lists the variables, values and describes the purpose of each
variable.
Value
Description
5
Channel 5 - location of SERIALISOL module
0
Trigger on False-to-True transition
16
Modbus Function Code "16" - Write Holding Registers
2
Length
8193
PowerFlex Logic Status word address + 1
2
PowerFlex Node address
{data}
PowerFlex Logic Command word
{data}
PowerFlex Speed Reference word