Allen-Bradley Micro800 General Instructions Manual page 185

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

Arguments
Parameter
Parameter
type
IN
Input
CtrlCfg
Input
SymbolicCfg
Input
TargetCfg
Input
Data
Input
Q
Output
Status
Output
DataLength
Output
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Data type
Description
BOOL
If Rising Edge (IN turns from FALSE to TRUE), start the function block with the
precondition that the last operation has been completed.
CIPCONTROLCFG
Function block execution control configuration.
See
CIPCONTROLCFG data type
CIPSYMBOLICCFG
Information for the symbol to Read/Write.
See
CIPSYMBOLICCFG data type
CIPTARGETCFG
Target device configuration.
See
CIPTARGETCFG data type
USINT[490]
Read command stores the data returned from the server.
Write command buffers the data to be sent to the server.
When a MSG is triggered or retriggered, Data is cleared for the MSG Read
command.
See
Supported Data Packet Size for CIP Serial Function
Tip: Refer to 2080-qs002_-en-e.pdf
BOOL
Outputs of this instruction are updated asynchronously from the program scan.
Output Q cannot be used to re-trigger the instruction since IN is edge triggered.
FALSE - The function block is not done.
TRUE - The function block is done.
CIPSTATUS
Function block execution status
When a MSG is triggered, or re-triggered, all elements inside Status are reset.
See
CIPSTATUS data type
UDINT
Number of data bytes Read/Written.
When a MSG is triggered or retriggered, DataLength is reset to 0 for MSG Read
command.
Communication instructions
on
page
177.
on
page
187.
on
page
180.
on
page
178.
Chapter 9
185