Modbus Error Codes - Allen-Bradley Micro800 General Instructions Manual

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

Structured Text (ST)

Modbus error codes

The following table describes error codes for the MSG_MODBUS function
block.
Error code
Error description
3
The value of the TriggerType has been changed from 2 - 255.
20
The local communication driver is incompatible with the MSG instruction.
21
A local channel configuration parameter error exists.
22
The Target or Local Bridge address is higher than the maximum node address.
33
A bad MSG file parameter exists.
54
A lost modem.
55
The message timed out in the local processor. A link layer timeout.
217
The user cancelled the message.
129
An illegal function.
130
An illegal data address.
131
An illegal data value.
132
A slave device failure.
133
Acknowledge.
134
The slave device is busy.
135
Negative acknowledge.
136
A memory parity error.
137
A non-standard reply.
255
The channel has been shut down.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Chapter 9
Communication instructions
199