Allen-Bradley Micro800 General Instructions Manual page 350

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

Chapter 14
High-Speed Counter (HSC) instructions
350
3. From the controller tree, click Embedded I/O, and
your encoder.
4. Verify the encoder is connected to the Micro830 controller.
5. Start the Micro830 controller and connect it to your computer.
6. Build the program and then download it to the controller.
Test the program and run the High-Speed Counter
After you download the HSC program to the controller, you can test it and then
run the High-Speed Counter.
To test the program
1. Connect to the Controller.
2. From the Project Organizer, double-click the HSC program, then double-
click Local Variables.
You can see the values of the two HSC outputs: STS (MyStatus) and
HSCSTS (MyInfo).
3. Double-click the _IO_EM_DI_05 direct contact to display the Variable
Selector window.
4. Click the I/O Micro830 tab, and then click the _IO_EM_DI_05 row.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
select input filters for

Advertisement

Table of Contents
loading

Table of Contents