Chapter 9
Communication instructions

MSG_CIPGENERIC

Parameter
IN
CtrlCfg
AppCfg
TargetCfg
ReqData
ReqLength
174
MSG_CIPGENERIC sends a common industrial protocol (CIP) explicit message
over an Ethernet channel or a serial port.
MSG_CIPGENERIC operation
A maximum of four message requests per channel can be processed in one scan.
For Ladder Diagram programs, message requests are executed at the end of a
ladder scan.
Arguments
When the MSG_CIPGENERIC function block is enabled, the receive buffers for
Read operations are cleared on the rising edge of Enable.
Parameter type
Data type
Input
BOOL
Input
CIPCONTROLCFG
Input
CIPAPPCFG
Input
CIPTARGETCFG
Input
USINT[1..1]
Input
UINT
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Description
If Rising Edge (IN turns from FALSE to TRUE), start the function block with the
precondition that the last operation has been completed.
Function block execution control configuration
See
CIPCONTROLCFG data type
on
page
CIP service and application path (EPATH) configuration
See
CIPAPPCFG data type
on
page
176.
Target device configuration
See
CIPTARGETCFG data type
on
page
CIP message request data. The array size should not be less than the
'ReqLength' size
See MSG_CIPGENERIC message behavior.
CIP message request data length:
• 0 - 490
177.
180.