TOF

Parameter
IN
PT
Q
ET
TOF increases an internal timer up to a given value.
Arguments
Parameter type
Data type
Input
BOOL
Input
TIME
Output
BOOL
Output
TIME
TOF timing diagram
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Timer instructions
Description
If falling edge, starts increasing internal timer.
If rising edge, stops and resets internal timer.
Maximum programmed time.
If TRUE: total time is not elapsed.
Current elapsed time. Possible values range from 0ms to
1193h2m47s294ms.
Tip: If you use the EN parameter with this block, the timer starts
incrementing when EN is set to TRUE, and continues to increment even if EN
is set to FALSE.