Arl - Allen-Bradley Micro800 General Instructions Manual

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

ARL

Parameter
Parameter type
IN
Input
ARLInput
Input
Q
Output
Destination
Output
NumChar
Output
Error
Output
ErrorID
Output
ARL reads characters from the buffer (up to and including the termination
characters) and stores them in a string.
Arguments
Data type
Description
BOOL
If Rising Edge (IN turns from FALSE to TRUE), start the function block with the precondition that the
last operation has been completed.
ARDARL
Read characters from the buffer (maximum is 82).
See
ARDARL data type
BOOL
Outputs of this instruction are updated asynchronously from the program scan. Output Q cannot be
used to re-trigger the instruction since IN is edge triggered.FALSE - The function block is not done.
TRUE - The function block is done.
ASCIILOCADDR
The string element where you want the characters stored.
UINT
The number of characters.
BOOL
FALSE - No error.
TRUE - An error is detected.
UINT
See
ABL error codes
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
ASCII serial port instructions
on
page
129.
on
page
127.
Chapter 6
121