UNF
Parameter
HSCSTS.UNF
The HSC sub-system sets the HSCSTS.UNF status flag to (1) whenever the
accumulated value (HSCSTS.Accumulator) has counted through the underflow
variable (HSCAPP.UFSetting). This bit is transitional and is set by the HSC sub-
system. It is up to the control program to use, track, and clear (0) the underflow
condition.
Underflow conditions do not generate a controller fault.
CountDir
Parameter
HSCSTS.CountDir
The HSC sub-system controls the HSCSTS.CountDir status flag. When the
HSC accumulator counts up, the direction flag is set to (1). Whenever the HSC
accumulator counts down, the direction flag is cleared (0).
If the accumulated value stops, the direction bit retains its value. The only time the
direction flag changes is when the accumulated count reverses.
This bit is updated continuously by the HSC sub-system whenever the controller
is in a run mode.
HPReached
Parameter
HSCSTS.HPReached
The HSC sub-system sets the HSCSTS.HPReached status flag to (1) whenever
the accumulated value (HSCSTS.Accumulator) is greater than or equal to the
high preset variable (HSCAPP.HPSetting).
This bit is updated continuously by the HSC sub-system whenever the controller
is in an executing mode. Writing to this element is not recommended.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Data type
HSC mode
BOOL
0...9
Data type
HSC mode
BOOL
0...9
Data type
BOOL
High-Speed Counter (HSC) instructions
User program access
read/write
User program access
read only
HSC mode
User program access
2...9
read/write
Chapter 14
323