Min. Panel Thickness | Screw Size | Screw Torque | DIN Rail |
1.9 mm (0.0747 in.) | M4 (#8-32) | 1.56-1.96 N-m (14-17 lb.-in.) | 35 mm |
Ambient Temperature | Enclosure Rating | Minimum Mounting Clearances | |
Minimum | Maximum | ||
-10°C (14°F) | 40°C (104°F) | IP 20/Open Type | Use Mounting Option A |
IP 30/NEMA 1/UL Type 1(1) | Use Mounting Option B | ||
50°C (122°F) | IP 20/Open Type | Use Mounting Option B |
The MOV to ground jumper must be removed if the drive is installed on an ungrounded or resistive grounded distribution system.
Tighten screw after jumper removal.
Drive Ratings | ||||||||||
Catalog Number | Output Ratings | Input Ratings | Branch Circuit Protection | Power Dissipation | ||||||
kW (HP) | Amps | Voltage Range | kVA | Amps | Fuses | 140M Motor Protectors(2)(3) | Contactors | Min. Enclosure Volume(4) (in.3) | IP20 Open Watts | |
100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output | ||||||||||
22A-V1P5N104 | 0.2 (0.25) | 1.5 | 90-126 | 0.75 | 6.0 | 10 | 140M-C2E-C10 | 100-C09 | 1655 | 32 |
22A-V2P3N104 | 0.4 (0.5) | 2.3 | 90-126 | 1.15 | 9.0 | 15 | 140M-C2E-C16 | 100-C12 | 1655 | 40 |
22A-V4P5N104 | 0.75 (1.0) | 4.5 | 90-126 | 2.25 | 18.0 | 30 | 140M-D8E-C20 | 100-C23 | 1655 | 55 |
22A-V6P0N104 | 1.1 (1.5) | 6.0 | 90-126 | 3.0 | 24.0 | 40 | 140M-F8E-C32 | 100-C37 | 1655 | 80 |
200 - 240V AC (±10%) – 1-Phase(1) Input, 0 - 230V 3-Phase Output, NO BRAKE | ||||||||||
22A-A1P4N103 | 0.2 (0.25) | 1.4 | 180-265 | 0.7 | 3.2 | 6 | 140M-C2E-B40 | 100-C09 | 1655 | 32 |
22A-A2P1N103 | 0.4 (0.5) | 2.1 | 180-265 | 1.05 | 5.3 | 10 | 140M-C2E-B63 | 100-C09 | 1655 | 40 |
22A-A3P6N103 | 0.75 (1.0) | 3.6 | 180-265 | 1.8 | 9.2 | 15 | 140M-C2E-C16 | 100-C12 | 1655 | 55 |
22A-A6P8N103 | 1.5 (2.0) | 6.8 | 180-265 | 3.4 | 14.2 | 25 | 140M-C2E-C16 | 100-C16 | 1655 | 85 |
22A-A9P6N103 | 2.2 (3.0) | 9.6 | 180-265 | 4.8 | 19.6 | 30 | 140M-D8E-C25 | 100-C23 | 1655 | 125 |
200 - 240V AC (±10%) – 1-Phase(1) Input, 0 - 230V 3-Phase Output | ||||||||||
22A-A1P5N104 | 0.2 (0.25) | 1.5 | 180-265 | 0.75 | 5.0 | 10 | 140M-C2E-B63 | 100-C09 | 1655 | 32 |
22A-A2P3N104 | 0.4 (0.5) | 2.3 | 180-265 | 1.15 | 6.0 | 10 | 140M-C2E-B63 | 100-C09 | 1655 | 40 |
22A-A4P5N104 | 0.75 (1.0) | 4.5 | 180-265 | 2.25 | 10.0 | 15 | 140M-C2E-C16 | 100-C12 | 1655 | 55 |
22A-A8P0N104 | 1.5 (2.0) | 8.0 | 180-265 | 4.0 | 18.0 | 30 | 140M-D8E-C20 | 100-C23 | 1655 | 85 |
200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output | ||||||||||
22A-B1P5N104 | 0.2 (0.25) | 1.5 | 180-265 | 0.75 | 1.8 | 3 | 140M-C2E-B25 | 100-C09 | 1655 | 32 |
22A-B2P3N104 | 0.4 (0.5) | 2.3 | 180-265 | 1.15 | 2.5 | 6 | 140M-C2E-B40 | 100-C09 | 1655 | 40 |
22A-B4P5N104 | 0.75 (1.0) | 4.5 | 180-265 | 2.25 | 5.2 | 10 | 140M-C2E-C10 | 100-C09 | 1655 | 55 |
22A-B8P0N104 | 1.5 (2.0) | 8.0 | 180-265 | 4.0 | 9.5 | 15 | 140M-C2E-C16 | 100-C12 | 1655 | 85 |
22A-B012N104 | 2.2 (3.0) | 12.0 | 180-265 | 5.5 | 15.5 | 25 | 140M-C2E-C16 | 100-C16 | 1655 | 125 |
22A-B017N104 | 3.7 (5.0) | 17.5 | 180-265 | 8.6 | 21.0 30 | 140M-F8E-C25 | 100-C23 | 1655 | 180 | |
380 - 480V AC (±10%) – 3-Phase Input, 0 - 460V 3-Phase Output | ||||||||||
22A-D1P4N104 | 0.4 (0.5) | 1.4 | 340-528 | 1.4 | 1.8 | 3 | 140M-C2E-B25 | 100-C09 | 1655 | 35 |
22A-D2P3N104 | 0.75 (1.0) | 2.3 | 340-528 | 2.3 | 3.2 | 6 | 140M-C2E-B40 | 100-C09 | 1655 | 50 |
22A-D4P0N104 | 1.5 (2.0) | 4.0 | 340-528 | 4.0 | 5.7 | 10 | 140M-C2E-B63 | 100-C09 | 1655 | 70 |
22A-D6P0N104 | 2.2 (3.0) | 6.0 | 340-528 | 5.9 | 7.5 | 15 | 140M-C2E-C10 | 100-C09 | 1655 | 100 |
22A-D8P7N104 | 3.7 (5.0) | 8.7 | 340-528 | 8.6 | 9.0 | 15 | 140M-C2E-C16 | 100-C16 | 1655 | 150 |
Input/Output Ratings
Output Frequency: 0-240 Hz (Programmable)
Efficiency: 97.5% (Typical)
Digital Control Inputs (Input Current = 6mA)
Analog Control Inputs
4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum
Control Output (Programmable Output, form C relay)
Resistive Rating: 3.0A at 30V DC, 125V AC and 240V AC
Inductive Rating: 0.5A at 30V DC, 125V AC, and 240V AC
Recommended Fuses and Circuit Breakers
Fuse: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Circuit Breakers: HMCP or Bulletin 140U or equivalent.
Protective Features
Dynamic Braking
Internal brake IGBT included with all ratings except No Brake versions.
Power Wire Rating | Recommended Copper Wire |
Unshielded 600V, 75°C (167°F) THHN/THWN | 15 Mils insulated, dry location |
Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2 | Belden 29501-29507 or equivalent |
Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2 | Shawflex 2ACD/3ACD or equivalent |
Power Terminal Block (A Frame Shown)
Terminal | Description | |
R/L1, S/L2 | 1-Phase Input | |
R/L1, S/L2, T/L3 | 3-Phase Input | |
U/T1 | To Motor U/T1 | = ![]() |
V/T2 | To Motor V/T2 | |
W/T3 | To Motor W/T3 | |
BR+, BR- | Dynamic Brake Resistor Connection [0.75 kW (1 HP) ratings and higher] | |
![]() | Safety Ground - PE |
Power Terminal Block Specifications
Frame | Maximum Wire Size(1) | Minimum Wire Size(1) | Torque |
A | 3.3 mm2 (12 AWG) | 0.8 mm2 (18 AWG) | 1.7-2.2 N-m (16-19 lb.-in.) |
B | 5.3 mm2 (10 AWG) | 1.3 mm2 (16 AWG) |
Input Power Conditions
Input Power Condition | Corrective Action |
Low Line Impedance (less than 1% line reactance) |
|
Greater than 120 kVA supply transformer | |
Line has power factor correction capacitors | |
Line has frequent power interruptions | |
Line has intermittent noise spikes in excess of 6000V (lightning) | |
Phase to ground voltage exceeds 125% of normal line to line voltage |
|
Ungrounded Distribution System |
Wire Type(s) | Description | Minimum Insulation Rating |
Belden 8760/9460 (or equiv.) | 0.8 mm2(18AWG), twisted pair, 100% shield with drain. | 300V 60 degrees C (140 degrees F) |
Belden 8770 (or equiv.) | 0.8 mm2(18AWG), 3 conductor, shielded for remote pot only. |
Maximum Wire Size(4) | Minimum Wire Size(4) | Torque |
1.3 mm2 (16 AWG) | 0.13 mm2 (26 AWG) | 0.5-0.8 N-m (4.4-7 lb.-in.) |
P036 [Start Source] | Stop | I/O Terminal 01 Stop |
Keypad | Per P037 | Coast |
3-Wire | Per P037 | Per P037 |
2-Wire | Per P037 | Coast |
RS485 Port | Per P037 | Coast |
30V DC | 125V AC | 240V AC | |
Resistive | 3.0A | 3.0A | 3.0A |
Inductive | 0.5A | 0.5A | 0.5A |
No. | Signal | Default | Description | Param. |
R1 | Relay N.O. | Fault | Normally open contact for output relay. | A055 |
R2 | Relay Common | – | Common for output relay. | |
R3 | Relay N.C. | Fault | Normally closed contact for output relay. | A055 |
Sink/Source DIP Switch | Source (SRC) | Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting. | ||
01 | Stop(1) | Coast | The factory installed jumper or a normally closed input must be present for the drive to start. | P036(1) |
02 | Start/Run FWD | Not Active | Command comes from the integral keypad by default. To disable reverse operation, see A095 [Reverse Disable]. | P036, P037 |
03 | Direction/Run REV | Not Active | P036, P037, A095 | |
04 | Digital Common | – | For digital inputs. Electronically isolated with digital inputs from analog I/O. | |
05 | Digital Input 1 | Preset Freq | Program with A051 [Digital In1 Sel]. | A051 |
06 | Digital Input 2 | Preset Freq | Program with A052 [Digital In2 Sel]. | A052 |
11 | +24V DC | – | Drive supplied power for digital inputs. Maximum output current is 100mA. | |
12 | +10V DC | – | Drive supplied power for 0-10V external potentiometer. Maximum output current is 15mA. | P038 |
13 | 0-10V In(3) | Not Active | For external 0-10V input supply (input impedance = 100k ohm) or potentiometer wiper. | P038 |
14 | Analog Common | – | For 0-10V In or 4-20mA In. Electronically isolated with analog inputs from digital I/O. | |
15 | 4-20mA In(3) | Not Active | For external 4-20mA input supply (input impedance = 250 ohm). | P038 |
16 | RS485 (DSI) Shield | – | Terminal should be connected to safety ground - PE when using the RS485 (DSI) communications port. |
ATTENTION: Power must be applied to the drive to perform the following start-up procedures. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove All Power including user supplied control voltages. User supplied voltages may exist even when main AC power is not applied to the drive. Correct the malfunction before continuing.
Before Applying Power to the Drive
Applying Power to the Drive
Factory default parameter values allow the drive to be controlled from the integral keypad. No programming is required to start, stop, change direction and control speed directly from the integral keypad.
To disable reverse operation, see A095 [Reverse Disable].
Menu | Description |
![]() | Display Group (View Only) Consists of commonly viewed drive operating conditions. |
![]() | Basic Program Group Consists of most commonly used programmable functions. |
![]() | Advanced Program Group Consists of remaining programmable functions. |
![]() | Fault Designator Consists of list of codes for specific fault conditions. Displayed only when fault is present. |
No. | LED | LED State | Description |
➊ | Run/Direction Status | Steady Red | Indicates drive is running and commanded motor direction. |
Flashing Red | Drive has been commanded to change direction. Indicates actual motor direction while decelerating to zero. | ||
➋ | Alphanumeric Display | Steady Red | Indicates parameter number, parameter value, or fault code. |
Flashing Red | Single digit flashing indicates that digit can be edited. All digits flashing indicates a fault condition. | ||
➌ | Displayed Units | Steady Red | Indicates the units of the parameter value being displayed. |
➍ | Program Status | Steady Red | Indicates parameter value can be changed. |
➎ | Fault Status | Flashing Red | Indicates drive is faulted. |
➏ | Pot Status | Steady Green | Indicates potentiometer on Integral Keypad is active. |
➐ | Start Key Status | Steady Green | Indicates Start key on Integral Keypad is active. The Reverse key is also active unless disabled by A095 [Reverse Disable]. |
No. | Key | Name | Description |
➑ | ![]() | Escape | Back one step in programming menu. Cancel a change to a parameter value and exit Program Mode. |
![]() | Select | Advance one step in programming menu. Select a digit when viewing parameter value. | |
![]() | Up Arrow Down Arrow | Scroll through groups and parameters. Increase/decrease the value of a flashing digit. | |
![]() | Enter | Advance one step in programming menu. Save a change to a parameter value. | |
➒ | ![]() | Potentiometer | Used to control speed of drive. Default is active. Controlled by parameter P038. |
![]() | Start | Used to start the drive. Default is active. Controlled by parameter P036. | |
![]() | Reverse | Used to reverse direction of the drive. Default is active. Controlled by parameters P036 and A095. | |
![]() | Stop | Used to stop the drive or clear a fault. This key is always active. Controlled by parameter P037. |
The last user-selected Display Group parameter is saved when power is removed and is displayed by default when power is reapplied.
The following is an example of basic integral keypad and display functions. This example provides basic navigation instructions and illustrates how to program the first Program Group parameter.
Step | Key(s) | Example Displays | ||
1 | When power is applied, the last user-selected Display Group parameter number is briefly displayed with flashing characters. The display then defaults to that parameter's current value. (Example shows the value of d001 [Output Freq] with the drive stopped.) | ![]() | ||
2 | Press Esc once to display the Display Group parameter number shown on power-up. The parameter number will flash. | ![]() | ![]() | |
3 | Press Esc again to enter the group menu. The group menu letter will flash. | ![]() | ![]() | |
4 | Press the Up Arrow or Down Arrow to scroll through the group menu (d, P and A). | ![]() | ||
5 | Press Enter or Sel to enter a group. The right digit of the last viewed parameter in that group will flash. | ![]() | ![]() | |
6 | Press the Up Arrow or Down Arrow to scroll through the parameters that are in the group. | ![]() | ||
7 | Press Enter or Sel to view the value of a parameter. If you do not want to edit the value, press Esc to return to the parameter number. | ![]() | ![]() | |
8 | Press Enter or Sel to enter program mode to edit the parameter value. The right digit will flash and the Program LED will illuminate if the parameter can be edited. | ![]() | ![]() | |
9 | Press the Up Arrow or Down Arrow to change the parameter value. If desired, press Sel to move from digit to digit or bit to bit. The digit or bit that you can change will flash. | ![]() | ||
10 | Press Esc to cancel a change. The digit will stop flashing, the previous value is restored and the Program LED will turn off. Or Press Enter to save a change. The digit will stop flashing and the Program LED will turn off. | ![]() | ||
![]() | ![]() | |||
11 | Press Esc to return to the parameter list. Continue to press Esc to back out of the programming menu. If pressing Esc does not change the display, then d001 [Output Frequency] is displayed. Press Enter or Sel to enter the group menu. | ![]() | ![]() |
No. | Parameter | Min/Max | Display/Options |
d001 | [Output Freq] | 0.0/[Maximum Freq] | 0.1 Hz |
d002 | [Commanded Freq] | 0.0/[Maximum Freq] | 0.1 Hz |
d003 | [Output Current] | 0.00/(Drive Amps × 2) | 0.01 Amps |
d004 | [Output Voltage] | 0/Drive Rated Volts | 1 VAC |
d005 | [DC Bus Voltage] | Based on Drive Rating | 1 VDC |
d006 | [Drive Status] | 0/1 (1 = Condition True) | Bit 3 Decelerating Bit 2 Accelerating Bit 1 Forward Bit 0 Running |
d007- d009 | [Fault x Code] | F2/F122 | F1 |
d010 | [Process Display] | 0.00/9999 | 0.01 – 1 |
d012 | [Control Source] | 0/9 | Digit 1 = Speed Command (See P038; 9 = "Jog Freq") Digit 0 = Start Command (See P036; 9 = "Jog") |
d013 | [Contrl In Status] | 0/1 (1 = Input Present) | Bit 3 Reserved Bit 2 Stop Input Bit 1 Dir/Run REV Bit 0 Start/Run FWD |
d014 | [Dig In Status] | 0/1 (1 = Input Present) | Bit 3 Reserved Bit 2 Reserved Bit 1 Digital In2 Sel Bit 0 Digital In1 Sel |
d015 | [Comm Status] | 0/1 (1 = Condition True) | Bit 3 Fault Occurred Bit 2 RS485 Option Bit 1 Transmitting Bit 0 Receiving |
d016 | [Control SW Ver] | 1.00/99.99 | 0.01 |
d017 | [Drive Type] | 1001/9999 | 1 |
d018 | [Elapsed Run Time] | 0/9999 Hrs | 1 = 10 Hrs |
d019 | [Testpoint Data] | 0/FFFF | 1 Hex |
d020 | [Analog In 0-10V] | 0.0/100.0% | 0.1% |
d021 | [Analog In 4-20mA] | 0.0/100.0% | 0.1% |
d024 | [Drive Temp] | 0/120 degC | 1 degC |
= Stop drive before changing this parameter.
No. | Parameter | Min/Max | Display/Options | Default |
P031![]() | [Motor NP Volts] | 20/Drive Rated Volts | 1 VAC | Based on Drive Rating |
Set to the motor nameplate rated volts. | ||||
P032![]() | [Motor NP Hertz] | 10/240 Hz | 1 Hz | 60 Hz |
Set to the motor nameplate rated frequency. | ||||
P033 | [Motor OL Current] | 0.0/(Drive Rated Amps×2) | 0.1 Amps | Based on Drive Rating |
Set to the maximum allowable motor current. | ||||
P034 | [Minimum Freq] | 0.0/240.0 Hz | 0.1 Hz | 0.0 Hz |
Sets the lowest frequency the drive will output continuously. | ||||
P035![]() | [Maximum Freq] | 0/240 Hz | 1 Hz | 60 Hz |
Sets the highest frequency the drive will output. | ||||
P036![]() | [Start Source] | 0/5 | 0 = "Keypad"(1) 1 = "3-Wire" 2 = "2-Wire" 3 = "2-W Lvl Sens" 4 = "2-W Hi Speed" 5 = "Comm Port" | 0 |
Sets the control scheme used to start the drive. | ||||
| ||||
P037 | [Stop Mode] | 0/7 | 0 = "Ramp, CF"(1) 1 = "Coast, CF" 2 = "DC Brake, CF"(1) 3 = "DCBrkAuto, CF"(1) 4 = "Ramp"(1) 5 = "Coast" 6 = "DC Brake" 7 = "DC BrakeAuto" | 0 |
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O Terminal 03), RS485 port] except as noted below. | ||||
I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set for "3-Wire" control. When in three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode].
| ||||
P038 | [Speed Reference] | 0/5 | 0 = "Drive Pot" 1 = "InternalFreq" 2 = "0-10V Input" 3 = "4-20mA Input" 4 = "Preset Freq" 5 = "Comm Port" | 0 |
Sets the source of the speed reference to the drive. | ||||
When A051 or A052 [Digital Inx Sel] is set to option 2, 4, 5, 6, 13 or 14, and the digital input is active, A051 or A052 will override the speed reference commanded by this parameter. | ||||
P039 | [Accel Time 1] | 0.0/600.0 Secs | 0.1 Secs | 10.0 Secs |
Sets the rate of accel for all speed increases. | ||||
P040 | [Decel Time 1] | 0.1/600.0 Secs | 0.1 Secs | 10.0 Secs |
Sets the rate of decel for all speed decreases. | ||||
P041![]() | [Reset To Defalts] | 0/1 | 0 = "Idle State" 1 = "Reset Defaults" | 0 |
Resets all parameter values to factory defaults. | ||||
P043 | [Motor OL Ret] | 0/1 | 0 = "Disabled" 1 = "Enabled" | 0 |
Enables/disables the Motor Overload Retention function. |
No. | Parameter | Min/Max | Display/Options | Default | ||||||||||||||||||||
A051 | [Digital In1 Sel] I/O Terminal 05 | 0/26 | 0 = "Not Used" 1 = "Acc 2 & Dec 2" 2 = "Jog" 3 = "Aux Fault" 4 = "Preset Freq" 5 = "Local" 6 = "Comm Port" 7 = "Clear Fault" 8 = "RampStop, CF" 9 = "CoastStop, CF" 10 = "DCInjStop, CF" 11 = "Jog Forward" 12 = "Jog Reverse" 13 = "10V In Ctrl" 14 = "20mA In Ctrl" 26 = "Anlg Invert" | 4 | ||||||||||||||||||||
A052![]() | [Digital In2 Sel] I/O Terminal 06 | |||||||||||||||||||||||
A055 | [Relay Out Sel] | 0/21 | 0 = "Ready/Fault" 1 = "At Frequency" 2 = "MotorRunning" 3 = "Reverse" 4 = "Motor Overld" 5 = "Ramp Reg" 6 = "Above Freq" 7 = "Above Cur" 8 = "Above DCVolt" 9 = "Retries Exst" 10 = "Above Anlg V" 20 = "ParamControl" 21 = "NonRec Fault" | 0 | ||||||||||||||||||||
A056 | [Relay Out Level] | 0.0/9999 | 0.1 | 0.0 | ||||||||||||||||||||
A067 | [Accel Time 2] | 0.0/600.0 Secs | 0.1 Secs | 20.0 Secs | ||||||||||||||||||||
A068 | [Decel Time 2] | 0.1/600.0 Secs | 0.1 Secs | 20.0 Secs | ||||||||||||||||||||
A069 | [Internal Freq] | 0.0/240.0 Hz | 0.1 Hz | 60.0 Hz | ||||||||||||||||||||
A070 | [Preset Freq 0](1) | 0.0/240.0 Hz | 0.1 Hz | 0.0 Hz | ||||||||||||||||||||
A071 | [Preset Freq 1] | 5.0 Hz | ||||||||||||||||||||||
A072 | [Preset Freq 2] | 10.0 Hz | ||||||||||||||||||||||
A073 | [Preset Freq 3] | 20.0 Hz | ||||||||||||||||||||||
| ||||||||||||||||||||||||
A078 | [Jog Frequency] | 0.0/[Maximum Freq] | 0.1 Hz | 10.0 Hz | ||||||||||||||||||||
A079 | [Jog Accel/Decel] | 0.1/600.0 Secs | 0.1 Secs | 10.0 Secs | ||||||||||||||||||||
A080 | [DC Brake Time] | 0.0/90.0 Secs | 0.1 Secs | 0.0 Secs | ||||||||||||||||||||
A081 | [DC Brake Level] | 0.0/(Drive Amps × 1.8) | 0.1 Amps | Amps × 0.05 | ||||||||||||||||||||
A082![]() | [DB Resistor Sel] | 0/99 | 0 = Disabled 1 = Normal RA Res 2 = NoProtection 3-99 = % of Duty Cycle | 0 | ||||||||||||||||||||
A083 | [S Curve %] | 0/100% | 1% | 0% (Disabled) | ||||||||||||||||||||
A084 | [Start Boost] | 1/14 | Settings in % of base voltage. Variable Torque 1 = "30.0, VT" 2 = "35.0, VT" 3 = "40.0, VT" 4 = "45.0, VT" Constant Torque 5 = "0.0, no IR" 6 = "0.0" 7 = "2.5, CT" 8 = "5.0, CT" 9 = "7.5, CT" 10 = "10.0, CT" 11 = "12.5, CT" 12 = "15.0, CT" 13 = "17.5, CT" 14 = "20.0, CT" | 8 7 (5 HP Drives) | ||||||||||||||||||||
A088 | [Maximum Voltage] | 20/Rated Volts | 1 VAC | Rated Volts | ||||||||||||||||||||
A089 | [Current Limit] | 0/(Drive Amps × 1.8) | 0.1 Amps | Amps × 1.5 | ||||||||||||||||||||
A090 | [Motor OL Select] | 0/2 | 0 = "No Derate" 1 = "Min Derate" 2 = "Max Derate" | 0 | ||||||||||||||||||||
A091 | [PWM Frequency] | 2.0/16.0 kHz | 0.1 kHz | 4.0 kHz | ||||||||||||||||||||
A092 | [Auto Rstrt Tries] | 0/9 | 1 | 0 | ||||||||||||||||||||
A093 | [Auto Rstrt Delay] | 0.0/300.0 Secs | 0.1 Secs | 1.0 Secs | ||||||||||||||||||||
A094![]() | [Start At PowerUp] | 0/1 | 0 = "Disabled" 1 = "Enabled" | 0 | ||||||||||||||||||||
A095![]() | [Reverse Disable] | 0/1 | 0 = "Rev Enabled" 1 = "Rev Disabled" | 0 | ||||||||||||||||||||
A096 | [Flying Start En] | 0/1 | 0 = "Disabled" 1 = "Enabled" | 0 | ||||||||||||||||||||
A097 | [Compensation] | 0/3 | 0 = "Disabled" 1 = "Electrical" 2 = "Mechanical" 3 = "Both" | 1 | ||||||||||||||||||||
A098 | [SW Current Trip] | 0.0/(Drive Amps × 2) | 0.1 Amps | 0.0 (Disabled) | ||||||||||||||||||||
A099 | [Process Factor] | 0.1/999.9 | 0.1 | 30.0 | ||||||||||||||||||||
A100![]() | [Fault Clear] | 0/2 | 0 = "Ready/Idle" 1 = "Reset Fault" 2 = "Clear Buffer" | 0 | ||||||||||||||||||||
A101 | [Program Lock] | 0/1 | 0 = "Unlocked" 1 = "Locked" | 0 | ||||||||||||||||||||
A102 | [Testpoint Sel] | 0/FFFF | 1 Hex | 400 | ||||||||||||||||||||
A103 | [Comm Data Rate](3) | 0/5 | 0 = "1200" 1 = "2400" 2 = "4800" 3 = "9600" 4 = "19.2K" 5 = "38.4K" | 3 | ||||||||||||||||||||
A104 | [Comm Node Addr](3) | 1/247 | 1 | 100 | ||||||||||||||||||||
A105 | [Comm Loss Action] | 0/3 | 0 = "Fault" 1 = "Coast to Stop" 2 = "Stop" 3 = "Continu Last" | 0 | ||||||||||||||||||||
A106 | [Comm Loss Time] | 0.1/60.0 | 0.1 | 5.0 | ||||||||||||||||||||
A107 | [Comm Format](3) | 0/5 | 0 = "RTU 8-N-1" 1 = "RTU 8-E-1" 2 = "RTU 8-O-1" 3 = "RTU 8-N-2" 4 = "RTU 8-E-2" 5 = "RTU 8-O-2" | 0 | ||||||||||||||||||||
A110 | [Anlg In 0-10V Lo] | 0.0/100.0% | 0.1% | 0.0% | ||||||||||||||||||||
A111 | [Anlg In 0-10V Hi] | 0.0/100.0% | 0.1% | 100.0% | ||||||||||||||||||||
A112 | [Anlg In4-20mA Lo] | 0.0/100.0% | 0.1% | 0.0% | ||||||||||||||||||||
A113 | [Anlg In4-20mA Hi] | 0.0/100.0% | 0.1% | 100.0% | ||||||||||||||||||||
A114 | [Slip Hertz @ FLA] | 0.0/10.0 Hz | 0.1 Hz | 2.0 Hz | ||||||||||||||||||||
A115 | [Process Time Lo] | 0.00/99.99 | 0.01 | 0.00 | ||||||||||||||||||||
A116 | [Process Time Hi] | 0.00/99.99 | 0.01 | 0.00 | ||||||||||||||||||||
A117 | [Bus Reg Mode] | 0/1 | 0 = "Disabled" 1 = "Enabled" | 1 | ||||||||||||||||||||
A118 | [Comm Write Mode] | 0/1 | 0 = "Save" 1 = "RAM Only" | 0 |
To clear a fault, press the Stop key, cycle power or set A100 [Fault Clear] to 1 or 2.
No. | Fault | Description |
F2 | Auxiliary Input(1) | Check remote wiring. |
F3 | Power Loss | Monitor the incoming AC line for low voltage or line power interruption. |
F4 | UnderVoltage(1) | Monitor the incoming AC line for low voltage or line power interruption. |
F5 | OverVoltage(1) | Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option. |
F6 | Motor Stalled(1) | Increase [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit]. |
F7 | Motor Overload(1) | An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. |
F8 | Heatsink OvrTmp(1) | Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded 40°C (104°F) for IP 30/NEMA 1/UL Type 1 installations or 50°C (122°F) for Open type installations. Check fan. |
F12 | HW OverCurrent(1) | Check programming. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess current. |
F13 | Ground Fault | Check the motor and external wiring to the drive output terminals for a grounded condition. |
F33 | Auto Rstrt Tries | Correct the cause of the fault and manually clear. |
F38 | Phase U to Gnd | Check the wiring between the drive and motor. Check motor for grounded phase. Replace drive if fault cannot be cleared. |
F39 | Phase V to Gnd | |
F40 | Phase W to Gnd | |
F41 | Phase UV Short | Check the motor and drive output terminal wiring for a shorted condition. Replace drive if fault cannot be cleared. |
F42 | Phase UW Short | |
F43 | Phase VW Short | |
F48 | Params Defaulted | The drive was commanded to write default values to EEPROM. Clear the fault or cycle power to the drive. Program the drive parameters as needed. |
F63 | SW OverCurrent(1) | Check load requirements and A098 [SW Current Trip] setting. |
F64 | Drive Overload | Reduce load or extend Accel Time. |
F70 | Power Unit | Cycle power. Replace drive if fault cannot be cleared. |
F71 | Net Loss | The communication network has faulted. |
F81 | Comm Loss | If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. Check connection. An adapter was intentionally disconnected. Turn off using A105 [Comm Loss Action]. |
F100 | Parameter Checksum | Restore factory defaults. |
F122 | I/O Board Fail | Cycle power. Replace drive if fault cannot be cleared. |
PowerFlex 4 Panel Mount Drives – Ratings are in kW and (HP)
Frame | 120V AC – 1-Phase | 240V AC – 1-Phase No Brake | 240V AC – 1-Phase | 240V AC – 3-Phase | 480V AC – 3-Phase |
A | 0.2 (0.25) 0.37(0.5) | 0.2 (0.25) 0.37 (0.5) 0.75 (1.0) | 0.2 (0.25) 0.37 (0.5) 0.75 (1.0) | 0.2 (0.25) 0.37 (0.5) 0.75 (1.0) 1.5 (2.0) | 0.37 (0.5) 0.75 (1.0) 1.5 (2.0) |
B | 0.75(1.0) 1.1 (1.5) | 1.5 (2.0) 2.2 (3.0) | 1.5 (2.0) | 2.2 (3.0) 3.7 (5.0) | 2.2 (3.0) 3.7 (5.0) |
PowerFlex 4 Panel Mount Drives(1)– Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
Frame | a | b(2) | c | d | e(3) | f | g | Shipping Weight |
A | 80 (3.15) | 185 (7.28) | 136 (5.35) | 67 (2.64) | 152 (5.98) | 59.3 (2.33) | 140 (5.51) | 1.4 (3.1) |
B | 100 (3.94) | 213 (8.39) | 136 (5.35) | 87 (3.43) | 180 (7.09) | 87.4 (3.44) | 168 (6.61) | 2.2 (4.9) |
IP 30/NEMA 1/UL Type 1 Option Kit – Dimensions are in millimeters and (inches)
ATTENTION: The drive contains high voltage capacitors which take time to discharge after removal of mains supply. Before working on drive, ensure isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death.
Darkened display LEDs is not an indication that capacitors have discharged to safe voltage levels.
ATTENTION: Equipment damage and/or personal injury may result if parameter A092 [Auto Rstrt Tries] or A094 [Start At PowerUp] is used in an inappropriate application. Do not use this function without considering applicable local, national and international codes, standards, regulations or industry guidelines.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, "Guarding Against Electrostatic Damage" or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.
U.S. Allen-Bradley Drives Technical Support
Tel: (1) 262.512.8176,
Fax: (1) 262.512.2222,
Email: support@drives.ra.rockwell.com,
Online: www.ab.com/support/abdrives
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Allen-Bradley PowerFlex 4 - Adjustable Frequency AC Drive Quick Start Guide
Advertisement
Need help?
Do you have a question about the PowerFlex 4 and is the answer not in the manual?
Questions and answers