Allen-Bradley Micro800 General Instructions Manual page 490

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

Chapter 17
Motion control instructions
Value
09
10
11
12
13
16
128
490
MACRO ID
MC_FB_ERR_
VELOCITY
MC_FB_ERR_
SOFT_LIMIT
MC_FB_ERR_
HARD_LIMIT
MC_FB_ERR_
LOG_LIMIT
MC_FB_ERR_
ERR_ENGINE
MC_FB_ERR_
NOT_HOMED
MC_FB_ERR_
PARAM_MODIFIED
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Description
The axis is not operational because the motion profile requested in a function block conflicts with the
current axis velocity.
Possible causes:
• The function block requests the axis to reverse the direction while the axis is moving.
• The current velocity is too low or too high for the requested motion profile.
Reset the state of the axis using the MC_Reset function block.
Correct the motion profile in the function block, or re-execute the function block when the axis velocity
is compatible with the requested motion profile.
The axis is not operational because
would cause a Soft Limit error.
Reset the state of the axis using the MC_Reset function block.
Check the velocity or target position settings for the function block, or adjust Soft Limit setting.
The axis is not operational because a Hard Limit error was detected.
Reset the state of the axis using the MC_Reset function block, and then move the axis away from the
Hard Limit switch in the opposite direction.
The axis is not operational because a PTO Accumulator logic limit error was detected, or executing the
function block would cause a PTO Accumulator logic limit error.
Reset the state of the axis using the MC_Reset function block.
Check the velocity or target position settings for the function block. Use the MC_SetPosition function
block to adjust the axis coordinate system.
The axis is not operational because a motion engine execution error was detected.
Power cycle the entire machine and download the User Application to the controller again.
If the fault persists, contact your local Rockwell Automation technical support representative. For
contact information, see: http://www.rockwellautomation.com/support.
The axis is not operational because the axis is not homed.
Reset the state of the axis using the MC_Reset function block.
Execute homing against the axis using MC_Home function block.
Motion internal warning, Warning ID = 0x80.
Contact your local Rockwell Automation technical support representative. For contact information, see:
http://www.rockwellautomation.com/support.
a Soft Limit error was detected, or executing the function block