Allen-Bradley Micro800 General Instructions Manual page 356

Programmable controllers
Hide thumbs Also See for Micro800:
Table of Contents

Advertisement

Chapter 14
High-Speed Counter (HSC) instructions
356
PLS enabled results
For this example, the following events will occur.
When the ladder logic first runs: HSCSTS.Accumulator = 1, which means
all the outputs are turned off.
When HSCSTS.Accumulator = 250, HSC_PLS[1].HSCHPOutput is sent
through the HSCAPP.OutputMask, and energizes outputs 0 and 1.
Sending the high preset output throught the output mask repeats as the
HSCSTS.Accumulator reaches 500, 750, and 1000, and the controller
energizes outputs 0...2, 0...3, and 0...4 respectively.
After the full operation completes, the cycle resets and repeats from
HSCSTS.HP = 250.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015