Connection Macro Cn002 - Control From Terminals (Pnp/Npn) - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning

Connection macro Cn002 - Control from terminals (PNP/NPN)

External control - Potentiometer with setpoint
● Hand/Auto switch between the BOP and terminals by pressing
● Both NPN and PNP can be realized with the same parameters. You can change the
connection of the digital input common terminal to 24 V or 0 V to decide the mode.
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P0771[0]
CI: Analog output
66
Factory default
Default for Cn002
1
2
1
2
0
1
0
12
9
9
15
10
21
21
+
Remarks
Terminal as command source
Analog as speed setpoint
ON/OFF
Reverse
Fault acknowledgement
JOG forward
Actual frequency
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884