Connection Macro Cn006 - External Push Button Control - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning
Parameter Description
P1016[0]
Fixed frequency mode
P1020[0]
BI: Fixed frequency selection
bit 0
P1021[0]
BI: Fixed frequency selection
bit 1
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1074[0]
BI: Disable additional setpoint 0
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1 52.3
P0732[0]
BI: Function of digital output 2 52.7

Connection macro Cn006 - External push button control

Note that the command sources are pulse signals.
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source 1
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P0727[0]
Selection of 2/3-wire method
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1 52.3
70
Factory default
Default for Cn005
1
1
722.3
722.1
722.4
722.2
10
10
15
15
1025.0
21
21
52.2
52.3
Factory default
Default for Cn006
2
1
1
0
2
0
1
9
13
15
14
0
3
21
21
52.2
Remarks
Direct selection mode
DI2
DI3
Fixed speed 1
Fixed speed 2
FF disables the additional setpoint
Actual frequency
Inverter running
Inverter fault active
Remarks
Terminals as command source
MOP as setpoint
OFF1/hold
ON pulse
MOP up pulse
MOP down pulse
3-wire
ON pulse + OFF1/hold + Reverse
Actual frequency
Inverter running
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884