Parameter list
7.2 Parameter list
Parameter
Function
P0704[0...2]
Function of digital input 4 0 - 99
Selects function of digital input 4.
See P0701.
P0712[0...2]
Analog / digital input 1
Selects function of digital input AI1 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0713[0...2]
Analog / digital input 2
Selects function of digital input AI2 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717
Connection macro
Selects a given connection macro, which is a set of parameter values for a given set of control connec-
tions. There are a number of connection macros which define basic control connection settings such as
Terminals, BOP, PID with analog setpoint etc.
Note:
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2]
Selection of command &
frequency setpoint
Central switch to select control command source for inverter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command / setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0
1
2
3
4
5
7
40
41
42
43
44
45
47
50
51
52
53
54
55
178
Range
Factory
Can be
default
changed
15
T
0 - 99
0
T
0 - 99
0
T
0 - 255
0
C(1)
0 - 57
0
T
Cmd = BICO parameter, Setpoint = BICO parameter
Cmd = BICO parameter, Setpoint = MOP setpoint
Cmd = BICO parameter, Setpoint = Analog setpoint
Cmd = BICO parameter, Setpoint = Fixed frequency
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
Cmd = BICO parameter, Setpoint = Analog setpoint 2
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)
Cmd = USS on RS232 (reserved), Setpoint = USS/MODBUS on RS485
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
Cmd = USS/MODBUS on RS485, Setpoint = BICO parameter
Cmd = USS/MODBUS on RS485, Setpoint = MOP setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Fixed frequency
Cmd = USS/MODBUS on RS485, Setpoint = USS on RS232 (reserved)
Cmd = USS/MODBUS on RS485, Setpoint = USS/MODBUS on RS485
Scaling
Data
Data
set
type
-
CDS
U16
-
CDS
U16
-
CDS
U16
-
-
U16
-
CDS
U16
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Acc.
Level
2
2
2
1
4