Siemens SINAMICS V20 Operating Instructions Manual page 160

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter list
7.2 Parameter list
Parameter
Function
Displays valid maximum output current of inverter.
r0067 is influenced/determined by the following factors:
Inverter application P0205
Rated motor current P0305
Motor overload factor P0640
Motor protection in dependency of P0610
r0067 is less than or equal to maximum inverter current r0209
Inverter protection in dependency of P0290
Note:
A reduction of r0067 may indicate an inverter overload or a motor overload.
r0068
CO: Output current [A] -
Displays unfiltered [rms] value of motor current. This value is available filtered (r0027) and unfiltered
(r0068).
Note:
Used for process control purposes (in contrast to r0027, which is filtered and is used to display the value
through USS).
r0069[0...5]
CO: Actual phase
currents [A]
Displays measured phase currents.
Index:
[0]
[1]
[2]
[3]
[4]
[5]
r0070
CO: Actual DC-link
voltage [V]
Displays DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Note:
Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered).
r0071
CO: Maximum output
voltage [V]
Displays maximum output voltage.
Dependency:
Actual maximum output voltage depends on the actual input supply voltage.
r0072
CO: Actual output
voltage [V]
Displays output voltage. This value is available filtered (r0025) and unfiltered (r0072).
r0074
CO: Actual modulation
[%]
Displays actual modulation index. The modulation index is defined as ratio between the magnitude of the
fundamental component in the inverter phase output voltage and half of the DC-link voltage.
r0078
CO: Actual current Isq
[A]
Displays component of torque generating current. This value is available filtered (r0030) and unfiltered
(r0078).
160
Range
Factory
default
-
-
-
U_Phase / Emitter1/
Dclink / Emitter2
Dclink
Offset U_phase / Emitter
Offset dclink
Not used
-
-
-
-
-
-
-
-
-
-
Can be
Scaling
changed
-
P2002
-
P2002
-
-
-
-
-
-
-
PERCENT
-
P2002
Operating Instructions, 09/2014, A5E34559884
Data
Data
Acc.
set
type
Level
-
Float
3
-
Float
4
-
Float
3
-
Float
3
-
Float
3
-
Float
4
-
Float
3
SINAMICS V20 Inverter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents