Commissioning
5.6 Function commissioning
5.6.2.2

Running the inverter in JOG mode

Functionality
The JOG function can be controlled by either the (built-in) BOP or the digital inputs. When
controlled by the BOP, pressing the RUN button will cause the motor to start and rotate at
the pre-set JOG frequency (P1058). The motor stops when the RUN button is released.
When using the digital inputs as the JOG command source, the JOG frequency is set by
P1058 for JOG right and P1059 for JOG left.
The JOG function allows:
● to check the functionality of the motor and inverter after commissioning has been
completed (first traversing motion, checking the direction of rotation, etc.)
● to bring a motor or a motor load into a specific position
● to traverse a motor, e.g. after a program has been interrupted
Setting parameters
Parameter
Function
P1055[0...2]
BI: Enable JOG right
P1056[0...2]
BI: Enable JOG left
P1057
JOG enable
P1058[0...2]
JOG frequency [Hz]
P1059[0...2]
JOG frequency left [Hz]
86
Setting
This parameter defines source of JOG right when P0719 = 0
(Auto selection of command / setpoint source).
Factory default: 19.8
This parameter defines source of JOG left when P0719 = 0
(Auto selection of command / setpoint source).
Factory default: 0
= 1: Jogging is enabled (default)
This parameter determines the frequency at which the inverter
will run while jogging is active.
Range: 0.00 to 550.00 (factory default: 5.00)
This parameter determines the frequency at which the inverter
will run while JOG left is selected.
Range: 0.00 to 550.00 (factory default: 5.00)
Operating Instructions, 09/2014, A5E34559884