Commissioning
5.5 Quick commissioning
Setting application macros

Application macro AP010 - Simple pump applications

Parameter Description
P1080[0]
Minimum frequency
P1300[0]
Control mode
P1110[0]
BI: Inhibit negative frequen-
cy setpoint
P1210[0]
Automatic restart
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time

Application macro AP020 - Simple fan applications

Parameter Description
P1110[0]
BI: Inhibit negative frequency
setpoint
P1300[0]
Control mode
P1200[0]
Flying start
P1210[0]
Automatic restart
P1080[0]
Minimum frequency
76
Factory default
Default for
AP010
0
15
0
7
0
1
1
2
10
10
10
10
Factory de-
Default for
fault
AP020
0
1
0
7
0
2
1
2
0
20
Remarks
Inverter running at a lower speed inhibited
Quadratic V/f
Reverse pump rotation inhibited
Fault acknowledgement at power-on
Ramp-up time from zero to maximum fre-
quency
Ramp-down time from maximum frequency
to zero
Remarks
Reverse fan rotation inhibited
Quadratic V/f
Search for the speed of the running motor
with a heavy inertia load so that the motor
runs up to the setpoint
Fault acknowledgement at power-on
Inverter running at a lower speed inhibited
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884