Parameter
Function
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the im-
portant parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be en-
tered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero automati-
cally.
P0010 = 2
For service purposes only.
P0010 = 30
When resetting the parameters or user default values of inverter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1. The inverter will automati-
cally reset all its parameters to their default settings. This can prove beneficial if you experience prob-
lems during parameter setup and wish to start again.
Resetting of the user default values will be started by setting parameter P0970 = 21. The inverter will
automatically reset all its parameters to the factory default settings. Duration of factory setting will take
about 60 seconds.
P0011
Lock for user-defined
parameter
See P0013
P0012
Key for user-defined
parameter
See P0013
P0013[0...19] User-defined parame-
ter
Defines a limited set of parameters to which the end user has access.
Instructions for use:
1. Set P0003 = 3 (expert user).
2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4. Set P0003 = 0 to activate the user defined parameter.
Index:
[0]
[1]
...
[19]
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
default
0 - 65535
0
0 - 65535
0
0 - 65535
[0...16] 0
[17] 3
[18] 10
[19] 12
1st user parameter
2nd user parameter
...
20th user parameter
Can be
Scaling
changed
U, T
-
U, T
-
U, T
-
Parameter list
7.2 Parameter list
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
3
-
U16
3
153