Issue 03/01
2.5.3
Control Cable Connections
1. Feed the control cables into the inverter via one of the gland holes at the I/O
module end of the terminal housing.
2. Run the control cable underneath the I/O board toward the control terminals.
3. Connect the control wires in accordance with the terminal information given in
Figure 2-11.
4. Use screened cable for all control wiring.
NOTE
If a PTC resistor is fitted, this
should be connected between 4
(+24 V) and 3 (DIN 3).
Terminal
1
2
3
6/7
8/9
Figure 2-11
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
Inputs
DIN 1
P0701 = '1'
DIN 2
P0702 = '12'
DIN 3
P0703 = '9'
AIN (-/+)
P0756 = 0
Option: DIN 4
P0704
Output Relay
P0731 = '52.3'
Control Terminals
Operating Instructions
8
1
2
3
Parameter
ON/OFF1
Reverse
Fault Acknowledge
0 – 10 V Analogue Input
0
Fault identification
2 Installation
9
4
5
6
7
Default operation