Parameter list
7.2 Parameter list
Parameter
Function
Setting:
722.0
722.1
722.2
r1114
CO: Freq. setpoint after
direction control [Hz]
Displays setpoint frequency after change of direction.
r1119
CO: Freq. setpoint be-
fore RFG [Hz]
Displays frequency setpoint at the input to the ramp function generator after modification by other func-
tions, e.g.:
P1110 BI: Inhibit neg. freq. setpoint,
P1091 - P1094 skip frequencies,
P1080 min. frequency,
P1082 max. frequency,
This value is available filtered (r0020) and unfiltered (r1119).
P1120[0...2]
Ramp-up time [s]
Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no
rounding is used. Setting the ramp-up time too short can cause the inverter to trip (overcurrent F1).
Dependency:
Rounding times (P1130 - P1133) and rounding type (P1134) will also have influence on the ramp.
See also P3350, P3353.
Notice:
Ramp times will be used as follows:
P1060 / P1061 : JOG mode is active
P1120 / P1121 : Normal mode (ON / OFF) is active
P1060 / P1061 : Normal mode (ON / OFF) and P1124 is active
Note:
If an external frequency setpoint with set ramp rates is used (e.g. from a PLC), the best way to achieve
optimum inverter performance is to set ramp times in P1120 and P1121 slightly shorter than those of the
PLC. Changes to P1120 will be immediately effective. If the SuperTorque function is enabled, the inverter
will initially ramp using the value in P3353.
P1121[0...2]
Ramp-down time [s]
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no
rounding is used.
Dependency:
See also P3350, P3353.
Notice:
Setting the ramp-down time too short can cause the inverter to trip (overcurrent F1 / overvoltage F2).
See P1120
Note:
Changes to P1121 will be immediately effective.
See P1120
P1124[0...2]
BI: Enable JOG ramp
times
Defines source for switching between jog ramp times (P1060, P1061) and normal ramp times (P1120,
P1121) as applied to the RFG. This parameter is valid for normal mode (ON / OFF) only.
Dependency:
See also P1175.
Notice:
P1124 does not have any impact when JOG mode is selected. In this case, jog ramp times (P1060,
P1061) will be used all the time. If the Dual Ramp function is selected using P1175, ramp times will switch
between normal (P1120, P1121) and JOG (P1060, P1061) ramp times, depending on the settings of
P2150, P2157 and P2159. Therefore, it is not recommended that JOG ramp is selected at the same time
as Dual Ramp.
See P1120.
206
Range
Factory
Can be
default
changed
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
-
-
-
-
-
-
0.00 -
10.00
C, U, T
650.00
0.00 -
10.00
C, U, T
650.00
0 -
0
T
4294967295
Scaling
Data
Data
set
type
-
-
Float
-
-
Float
-
DDS
Float
-
DDS
Float
-
CDS
U32
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Acc.
Level
3
3
1
1
3