Parameter list
7.2 Parameter list
Parameter
Function
P1023[0...2]
BI: Fixed frequency
selection Bit 3
See P1020
r1024
CO: Actual fixed fre-
quency [Hz]
Displays sum total of selected fixed frequencies.
r1025.0
BO: Fixed frequency
status
Displays the status of fixed frequencies.
Bit
00
P1031[0...2]
MOP mode
MOP mode specification.
Bit
00
01
Note:
Defines the operation mode of the motorized potentiometer. See P1040.
P1032
Inhibit reverse direction
of MOP
Inhibits reverse setpoint selection of the MOP.
0
1
Note:
It is possible to change motor direction using the motor potentiometer setpoint (increase / decrease fre-
quency).
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase / decrease
frequency).
If P1032 = 1 and P1000 = 1 or 1X, then reverse motor direction will be inhibited.
P1035[0...2]
BI: Enable MOP (UP-
command)
Defines source for motor potentiometer setpoint increase frequency.
Setting:
722.0
722.1
722.2
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator accelerates with the rate of
P1047.
P1036[0...2]
BI: Enable MOP
(DOWN-command)
Defines source for motor potentiometer setpoint decrease frequency.
Setting:
See P1035
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator decelerates with the rate of
P1048.
200
Range
0 -
4294967295
-
-
Signal name
Status of FF
0 - 3
Signal name
Setpoint store active
No On-state for MOP necessary
0 - 1
Reverse direction is allowed
Reverse direction inhibited
0 -
4294967295
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
0 -
4294967295
Factory
Can be
default
changed
722.6
T
-
-
-
-
1
U, T
1
T
19.13
T
19.14
T
Operating Instructions, 09/2014, A5E34559884
Scaling
Data
Data
set
type
-
CDS
U32
-
-
Float
-
-
U16
1 signal
0 signal
Yes
No
-
DDS
U16
1 signal
0 signal
Yes
No
Yes
No
-
-
U16
-
CDS
U32
-
CDS
U32
SINAMICS V20 Inverter
Acc.
Level
3
3
3
2
2
3
3