7.2 Parameter list
Parameter
Function
P2810[0], P2810[1] define inputs of AND 1 element, output is r2811.
Index:
[0]
[1]
Dependency:
P2801[0] assigns the AND element to the processing sequence.
r2811.0
BO: AND 1
Output of AND 1 element. Displays and logic of bits defined in P2810[0], P2810[1].
Bit
00
Dependency:
See P2810
P2812[0...1]
BI: AND 2
P2812[0], 2812[1] define inputs of AND 2 element, output is r2813.
Index:
See P2810
Dependency:
P2801[1] assigns the AND element to the processing sequence.
r2813.0
BO: AND 2
Output of AND 2 element. Displays and logic of bits defined in P2812[0], P2812[1]. See r2811 for the bit
field description.
Dependency:
See P2812
P2814[0...1]
BI: AND 3
P2814[0], P2814[1] define inputs of AND 3 element, output is r2815.
Index:
See P2810
Dependency:
P2801[2] assigns the AND element to the processing sequence.
r2815.0
BO: AND 3
Output of AND 3 element. Displays and logic of bits defined in P2814[0], P2814[1]. See r2811 for the bit
field description.
Dependency:
See P2814
P2816[0...1]
BI: OR 1
P2816[0], P2816[1] define inputs of OR 1 element, output is r2817.
Index:
See P2810
Dependency:
P2801[3] assigns the OR element to the processing sequence.
r2817.0
BO: OR 1
Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1]. See r2811 for the bit field
description.
Dependency:
See P2816
260
Range
Binector input 0 (BI 0)
Binector input 1 (BI 1)
-
Signal name
Output of BO
0 -
4294967295
-
0 -
4294967295
-
0 -
4294967295
-
Factory
Can be
Scaling
default
changed
-
-
-
1 signal
Yes
0
U, T
-
-
-
-
0
U, T
-
-
-
-
0
U, T
-
-
-
-
Operating Instructions, 09/2014, A5E34559884
Data
Data
Acc.
set
type
Level
-
U16
3
0 signal
No
-
U32
3
-
U16
3
-
U32
3
-
U16
3
-
U32
3
-
U16
3
SINAMICS V20 Inverter