5.6 Function commissioning

Compound braking

For compound braking (enabled using P1236), DC braking is superimposed with
regenerative braking (where the inverter regenerates into the DC-link supply as it brakes
along a ramp). Effective braking is obtained without having to use additional components by
optimizing the ramp-down time (P1121 for OFF1 or when braking from f1 to f2, P1135 for
OFF3) and using compound braking P1236.
Setting parameters
Parameter
Function
P1236[0...2]
Compound braking current [%]
P1254
Auto detect Vdc switch-on levels
94
Setting
This parameter defines DC level superimposed on AC wave-
form after exceeding DC-link voltage threshold of compound
braking. The value is entered in [%] relative to rated motor
current (P0305).
Range: 0 to 250 (factory default: 0)
This parameter enables / disables auto-detection of switch-on
levels for Vdc_max controller.
= 0: Disabled
= 1: Enabled (factory default)
It is recommended to set P1254 = 1 (auto detection of Vdc
switch-on levels enabled). Note that auto detection only works
when the inverter has been in standby for over 20s.