Basic Inverter Settings - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Communicating with the PLC
6.1 USS communication
No.
Description
101
Parameter is currently deactivated; parameter has no function in the present inverter status
102
Communication channel width is insufficient for response; dependent on the number of PKW and the maximum
net data length of the inverter
104
Illegal parameter value
105
Parameter is indexed
106
Request is not included/task is not supported
109
PKW request access timeout/number of retries is exceeded/wait for response from CPU side
110
Parameter value cannot be changed (parameter is locked)
200/201
Changed lower/upper limits exceeded
202/203
No display on the BOP
204
The available access authorization does not cover parameter changes
300
Array elements differ

Basic inverter settings

Parameter
Function
P0010
Commissioning parameter
P0970
Factory reset
P0003
User access level
P0700
Selection of command source
P1000
Selection of frequency setpoint
P2023
RS485 protocol selection
P2010[0]
USS/MODBUS baudrate
P2011[0]
USS address
136
Setting
= 30: restores to factory settings
Possible settings:
= 1: resets all parameters (not user defaults) to their default
values
= 21: resets all parameters and all user defaults to factory
reset state
Note: Parameters P2010, P2011, P2023 retain their values
after a factory reset.
= 3
= 5: USS/MODBUS on RS485
Factory default: 1 (operator panel)
= 5: USS/MODBUS on RS485
Factory default: 1 (MOP setpoint)
= 1: USS (factory default)
Note: After changing P2023, powercycle the inverter. Dur-
ing the powercycle, wait until LED has gone off or the dis-
play has gone blank (may take a few seconds) before re-
applying power. If P2023 has been changed via a PLC,
make sure the change has been saved to EEPROM via
P0971.
Possible settings:
= 6: 9600 bps (factory default)
= 7: 19200 bps
= 8: 38400 bps
...
= 12: 115200 bps
Sets the unique address for the inverter.
Range: 0 to 31 (factory default: 0)
Operating Instructions, 09/2014, A5E34559884
SINAMICS V20 Inverter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents