Parameter
Function
P2946
Wobble signal ampli-
tude [%]
Sets the value for the amplitude of the wobble-signal as a proportion of the present ramp function genera-
tor (RFG) output. The value of P2946 is multiplied by the output value of the RFG then added to RFG out-
put.
For example, if the RFG output is 10 Hz, and P2946 has a value of 0.100, the wobble signal amplitude will
be 0.100 * 10 = 1 Hz. This means that the RFG output will therefore wobble between 9 Hz and 11 Hz.
P2947
Wobble signal decre-
ment step
Sets the value for decrement step at the end of the positive signal period. The amplitude of the step is
dependant upon the signal amplitude as follows:
Amplitude of signal decrement step = P2947 * P2946
P2948
Wobble signal incre-
ment step
Sets the value for the increment step at the end of the negative signal period. The amplitude of the incre-
ment step is dependant upon the signal amplitude as follows:
Amplitude of signal increment step = P2948 * P2946
P2949
Wobble signal pulse
width [%]
Sets the relative widths of the rising and falling pulses. The value in P2949 sets the proportion of the wob-
ble period (determined by P2945) allocated to the rising pulse, the remainder of the time is allocation to the
falling pulse.
A value of 60% in P2949 means that 60% of the wobble period the wobble output will be rising. For the
remaining 40% of the wobble period the wobble output will be falling.
r2955
CO: Wobble signal
output [%]
Displays the output of the wobble function.
r3113.0...15
CO / BO: Fault bit array
Gives information about actual fault.
Bit
00
01
02
03
04
05
06
07
09
10
11
12
13
14
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
0.000 -
0.200
0.000 -
1.000
0.000 -
1.000
0 - 100
-
-
Signal name
Inverter error
Power line failure
Intermediate circuit power voltage
Error power electronics
Inverter overtemperature
Earth leakage
Motor overload
Bus fault
Reserved
Fault internal communication
Motor current limit
Supply failure
Reserved
Reserved
Factory
Can be
default
changed
0.000
T
0.000
T
0.000
T
50
T
-
-
-
-
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
-
-
Float
-
-
Float
-
-
Float
-
-
U16
-
-
Float
-
-
U16
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Acc.
Level
2
2
2
2
2
1
271

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents