Faults and alarms
8.1 Faults
Fault
F20
DC ripple too high
F35
Maximum number of auto
restart attempts exceeded
F41
Motor data identification
failure
F51
Parameter EEPROM fault
284
Cause
The calculated DC ripple level has ex-
ceeded the safe threshold. This is
commonly caused by loss of one of the
mains input phases.
Auto restart attempts exceed value of
P1211.
Motor data identification failed.
r0949 = 0: No load applied
r0949 = 1: Current limit level
reached during identification.
r0949 = 2: Identified stator re-
sistance less than 0.1% or greater
than 100%.
r0949 = 30: Current controller at
voltage limit
r0949 = 40: Inconsistency of identi-
fied dataset, at least one identifica-
tion failed
Percentage values based on the im-
pedance Zb = Vmot,nom / sqrt(3) /
Imot,nom
Read or write failure while access to
EEPROM. This can also be caused by
the EEPROM being full, too many pa-
rameters have been changed.
Remedy
Check the mains supply wiring.
Check the following:
r0949 = 0: is the motor connected to the invert-
er?
r0949 = 1 - 49: are the motor data in P0304 -
P0311 correct?
Check what type of motor wiring is required
(star, delta).
Must be power-cycled to cancel this bug as
some parameters may not be read correct.
Factory reset and new parameterization, if pow-
er-cycle does not remove fault.
Change some parameters back to default val-
ues if the EEPROM is full, then power-cycle.
Change inverter.
Note:
r0949 = 1: EEPROM full
r0949 = 1000 + block No: reading data block
failed
r0949 = 2000 + block No: reading data block
timeout
r0949 = 3000 + block No: reading data block
CRC failed
r0949 = 4000 + block No: writing data block
failed
r0949 = 5000 + block No: writing data block
timeout
r0949 = 6000 + block No: writing data block
verify failed
Operating Instructions, 09/2014, A5E34559884