Parameter
Function
0
2
Note:
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Ensure that enough space exists on the MMC card before transferring data (8kb).
P0803
Transfer data to
EEPROM
Transfers values from External to inverter when none 0. P0010 must be set to 30 for this to be possible.
See P0802 for parameter values.
Note:
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
P0804
Select Clone file
Select clone file to up / down load.
if P0804 = 0 then file name is clone00.bin
if P0804 = 1 then file name is clone01.bin
etc.
P0806
BI: Inhibit panel access
Binector input to lock control panel access through external client.
r0807.0
BO: Displays client ac-
cess
Binector output to display whether command and setpoint source is connected to an external client.
Bit
00
P0809[0...2]
Copy command data set
(CDS)
Calls 'Copy command data set (CDS)' function. The list of all command data sets (CDS) parameters is
shown in "Index" at the end of the manual.
Example:
Copying of all values from CDS0 to CDS2 can be accomplished by the following procedure:
P0809[0] = 0 Copy from CDS0
P0809[1] = 2 Copy to CDS2
P0809[2] = 1 Start copy
Index:
[0]
[1]
[2]
Note:
Start value in index 2 is automatically reset to '0' after execution of function.
P0810
BI: command data set bit
0 (Hand / Auto)
Selects command source from which to read Bit 0 for selecting a command data set (CDS). The actual
selected CDS is displayed in r0054.15 (CDS bit 0) and r0055.15 (CDS bit 1). The actual active CDS is
displayed in r0050.
Setting:
722.0
722.1
722.2
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Disabled
Start MMC Transfer
0 - 2
0 - 99
0 -
4294967295
-
Signal name
Master control active
0 - 2
Copy from CDS
Copy to CDS
Start copy
0 -
4294967295
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
Factory
Can be
Scaling
default
changed
0
C(30)
-
0
C(30)
-
0
U, T
-
-
-
-
1 signal
Yes
[0] 0 [1]
T
-
1 [2] 0
0
U, T
-
Parameter list
7.2 Parameter list
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
3
-
U32
3
-
U16
3
0 signal
No
-
U16
2
-
U32
2
187