Siemens SINAMICS V20 Operating Instructions Manual page 211

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
P1210 = 6:
The inverter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
inverter. It is necessary that the ON command is wired via a digital input (digital input). Setting 6 causes
the motor to restart immediately.
P1210 = 7:
The inverter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
inverter. It is necessary that the ON command is wired via a digital input (digital input). Setting 7 causes
the motor to restart immediately.
The difference between this mode and Mode 6 is that the fault status bit (r0052.3) is not set until the num-
ber of restarts defined by P1211 have been exhausted.
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1211
Number of restart at-
tempts
Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.
P1215
Holding brake enable
Enables / disables holding brake function. The motor holding brake (MHB) is controlled via status word 1
r0052 bit 12. This signal can be issued via:
status word of the serial interface (e.g. USS)
digital outputs (e.g. DO1: ==> P0731 = 52.C (r0052 bit 12))
0
1
Caution:
If the inverter controls the motor holding brake, then a commissioning may not be carried out for potentially
hazardous loads (e.g. suspended loads for crane applications) unless the load has been secured.
It is not permissible to use the motor holding brake as working brake, as it is generally only designed for a
limited number of emergency braking operations.
P1216
Holding brake release
delay[s]
Defines period during which inverter runs at minimum frequency P1080 before ramping up.
P1217
Holding time after ramp
down [s]
Defines time for which inverter runs at minimum frequency (P1080) after ramping down.
Note:
If P1217 > P1227, P1227 will take precedence.
P1218[0...2]
BI: Motor holding brake
override
Enables the motor holding brake output to be overridden, allowing the brake to be opened under separate
control.
P1227[0...2]
Zero speed detection
monitoring time [s]
Sets the monitoring time for the standstill identification.
When braking with OFF1 or OFF3, standstill is identified after this time has expired, after the setpoint
speed has fallen below P2167. After this, the braking signal is started, the system waits for the closing time
and then the pulses are cancelled.
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
Can be
default
changed
0 - 10
3
U, T
0 - 1
0
C, T
Motor holding brake disabled
Motor holding brake enabled
0.0 - 20.0
1.0
C, T
0.0 - 20.0
1.0
C, T
0 -
0
U, T
429496729
5
0.0 - 300.0
4.0
U, T
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
-
-
U16
-
-
U16
-
-
Float
-
-
Float
-
CDS
U32
-
DDS
Float
Acc.
Level
3
2
2
2
3
2
211