Parameter list
7.2 Parameter list
Parameter
Function
P0969
Resettable system run
time counter
Resettable system run time counter.
P0970
Factory reset
P0970 = 1 resets all parameters (not user defaults) to their default values.
P0970 = 21 resets all parameters and all user defaults to Factory Reset state.
0
1
21
Dependency:
First set P0010 = 30 (factory settings).
Stop inverter (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
r0039 CO: Energy consumption meter [kWh]
P0014 Store mode
P0100 Europe / North America
P0205 Inverter application
P2010 USS / MODBUS baudrate
P2011 USS address
P2021 MODBUS address
P2023 RS485 protocol selection
P8458 Clone control
When transferring P0970, the inverter uses its processor to carry out internal calculations. Communica-
tions are interrupted for the time that it takes to make these calculations.
P0971
Transfer data from RAM
to EEPROM
Transfers values from RAM to EEPROM when set to 1.
Transfers new user default values from RAM to EEPROM when set to 21.
0
1
21
Note:
All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the
transfer was successful. During the reset process communications will be interrupted.
BOP displays 88888
After completion of the transfer process, the communication between the inverter and external peripherals
(BOP, USS or Modbus Master) is automatically re-established.
r0980[0...99]
List of available parame-
ter numbers
Contains 100 parameter numbers index 0 - 99.
Index:
[0]
[1]
194
Range
Factory
Can be
default
changed
0 -
0
T
4294967295
0 - 21
0
C(30)
Disabled
Parameter reset
User Default Parameter Reset
0 - 21
0
U, T
Disabled
Start transfer
Start User Defaults transfer
0 - 65535
981
-
Parameter 1
Parameter 2
Scaling
Data
Data
set
type
-
-
U32
-
-
U16
-
-
U16
-
-
U16
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Acc.
Level
3
1
3
4