Parameter list
7.2 Parameter list
Parameter
Function
Notice:
Use setting 1 (low overload) only for low-overload applications (for example, pumps and fans).
If it is used for high-overload applications, I2t warning will be produced too late, causing overheating in the
motor.
Note:
This parameter selects inverter application for FSE only. The parameter value is not reset by the factory
setting (see P0970).
r0206
Rated inverter power
[kW] / [hp]
Displays nominal rated motor power from inverter.
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0207[0...2]
Rated inverter current
[A]
Displays rated inverter current.
Index:
[0]
[1]
[2]
Note:
The rated high overload (HO) current r0207[2] values correspond to suitable 4-pole Siemens standard
motors (IEC) for the selected load cycle (see diagram). r0207[2] is the default value of P0305 in associa-
tion with the HO application (load cycle).
r0208
Rated inverter voltage
[V]
Displays nominal AC supply voltage of inverter.
Note:
r0208 = 230: 200 V to 240 V (tolerance: -10% to +10%)
r0208 = 400: 380 V to 480 V (tolerance: -15% to +10%)
164
Range
Factory
default
-
-
-
-
Rated inverter current
Rated LO current
Rated HO current
-
-
Can be
Scaling
changed
-
-
-
-
-
-
Operating Instructions, 09/2014, A5E34559884
Data
Data
Acc.
set
type
Level
-
Float
2
-
Float
2
-
U32
2
SINAMICS V20 Inverter