Connection Terminals At The Inverter - Siemens SINAMICS PM240-2 Hardware Installation Manual

Power module for sinamics g120
Hide thumbs Also See for SINAMICS PM240-2:
Table of Contents

Advertisement

Table 5- 3
Inverter
EMC category
Cable
200 V
400 V
690 V
only C3
1)
5.2.3

Connection terminals at the inverter

Table 5- 4
Connection, cross-section and tightening torque for PM240-2 Power Modules
Inverters
FSA
Line supply, motor,
DC link and braking
FSB
resistor
FSC
FSD
Line supply, motor
and DC link
Braking resistor
FSE
Line supply, motor
and DC link
Braking resistor
FSF
Line supply, motor
and DC link
Braking resistor
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
Permissible cable lengths for the motor connection, FSF
with internal
C2 filter
Second Envi-
ronment, C2
Shielded
---
150 m
150 m
1)
Connection
Plug connector
with screw termi-
nals
Screw-type termi-
nal
Screw-type termi-
nal
Cable lug accord-
ing to SN71322
Screw-type termi-
nal
5.2 Connecting the line and motor cable at the inverter
with or without filter, with or
without output reactor
No EMC category
Shielded
Unshielded
300 m
450 m
300 m
450 m
300 m
450 m
Cross-section, tightening torque
Metric
1.5 ... 2.5 mm
, 0.5 Nm
2
1.5 ... 6 mm
, 0.6 Nm
2
6 ...16 mm², 1.3 Nm
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
2.5 ... 16 mm
,
2
1.2 ... 1.5 Nm
25 ... 70 mm
, 8 ... 10 Nm 6 ... 3/0 AWG,
2
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
35 ... 2 × 120 mm
,
2
22 ... 25 Nm
25 ... 70 mm
, 8 ... 10 Nm 6 ... 3/0 AWG,
2
Connecting-up
without filter, with two output
reactors in series
Shielded
Unshielded
525 m
525 m
525 m
Imperial
16 ... 14 AWG, 4.5 lbf in 8 mm
16 ... 10 AWG, 5.5 lbf in 8 mm
10 ... 6 AWG, 12 lbf in
20 ... 10 AWG, 22 lbf in
8 ... 2 AWG, 40 lbf in
20 ... 6 AWG, 15 lbf in
88.5 lbf in
20 ... 10 AWG, 22 lbf in
8 ... 2 AWG, 40 lbf in
1 ... 2 × 4/0 AWG,
210 lbf.in
88.5 lbf in
800 m
800 m
800 m
Stripped
insulation
length
10 mm
18 mm
10 mm
25 mm
18 mm
--
25 mm
53

Hide quick links: