Parameter list
7.2 Parameter list
Parameter
Function
Dependency:
First, set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined parame-
ter.
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
P0014[0...2]
Store mode
Sets the store mode for parameters. The store mode can be configured for all interfaces under "Index".
0
1
Index:
[0]
[1]
[2]
Note:
An independent store request may be part of the serial communications (for example, PKE bits 15-12 of
USS protocol). See the table below for an influence on the settings of P0014.
Value of P0014 [x]
EEPROM
EEPROM
1. P0014 itself will always be stored in the EEPROM.
2. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0970 = 1).
When transferring parameter P0014, the inverter uses its processor to carry-out internal calculations.
Communications - both via USS as well as Modbus - are interrupted for the time that it takes to make
these calculations.
r0018
Firmware version
Displays version number of installed firmware.
r0019.0...14
CO / BO: Operator
panel control word
Displays status of operator panel commands. The settings below are used as the "source" codes for key-
pad control when connecting to BICO input parameters.
Bit
00
01
08
11
13
14
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
r0020
CO: Frequency set-
point before RFG [Hz]
Displays actual frequency setpoint (input of ramp function generator). This value is available filtered
(r0020) and unfiltered (r1119). The actual frequency setpoint after RFG is displayed in r1170.
154
Range
0 - 1
Volatile ( RAM)
Non-volatile (EEPROM)
USS/Modbus on RS485
USS on RS232 (reserved)
Reserved
RAM
RAM
-
-
Signal name
ON / OFF1
OFF2: Electrical stop
JOG right
Reverse (setpoint inversion)
Motor potentiometer MOP up
Motor potentiometer MOP down
-
Factory
Can be
default
changed
0
U, T
Store request via USS
EEPROM
EEPROM
RAM
RAM
-
-
-
-
-
-
Operating Instructions, 09/2014, A5E34559884
Scaling
Data
Data
set
type
-
-
U16
Result
EEPROM
EEPROM
RAM
EEPROM
-
-
Float
-
-
U16
1 signal
0 signal
Yes
No
No
Yes
Yes
No
Yes
No
Yes
No
Yes
No
-
-
Float
SINAMICS V20 Inverter
Acc.
Level
3
1
3
3