Siemens SINAMICS V20 Operating Instructions Manual page 222

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter list
7.2 Parameter list
Parameter
Function
r1343
CO: Imax controller fre-
quency output [Hz]
Displays effective frequency limitation.
Dependency:
If I_max controller not in operation, parameter normally shows maximum frequency P1082.
r1344
CO: Imax controller volt-
age output [V]
Displays amount by which the I_max controller is reducing the inverter output voltage.
P1345[0...2]
Imax voltage controller
proportional gain
If the output current (r0068) exceeds the maximum current (r0067), the inverter is dynamically controlled
by reducing the output voltage. This parameter sets the proportional gain of this controller.
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
Note:
See P1340 for further information. The Factory setting depends on inverter power.
P1346[0...2]
Imax voltage controller
integral time [s]
Integral time constant of the I_max voltage controller.
P1341 = 0: I_max controller disabled
P1345 = 0 and P1346 > 0: I_max voltage controller enhanced integral
P1345 > 0 and P1346 > 0: I_max voltage controller normal PI control
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
Note:
See P1340 for further information. The Factory setting depends on inverter power.
r1348
Economy mode factor [%] -
Displays the calculated economy mode factor (range 80%-120%) applied to the demanded output volts.
Economy mode is used to find the most efficient operating point for a given load. It does this by a continu-
ous method of hill climbing optimization. Hill climbing optimization works by slightly changing the output
volts either up or down and monitoring the change in input power. If the input power has decreased, the
algorithm changes the output volts in the same direction. If the input power has increased then the algo-
rithm adjusts the output volts in the other direction. Using this algorithm, the software should be able to
find the minimum point on the graph between input power and output volts.
Notice:
If this value is too low, the system may become unstable.
P1350[0...2]
Voltage soft start
Sets whether voltage is built up smoothly during magnetization time (ON) or whether it simply jumps to
boost voltage (OFF).
0
1
Note:
The settings for this parameter bring benefits and drawbacks:
P1350 = 0: OFF (jump to boost voltage)
Benefit: flux is built up quickly
Drawback: motor may move
P1350 = 1: ON (smooth voltage build-up)
Benefit: motor less likely to move
Drawback: flux build-up takes longer
222
Range
Factory
Can be
default
changed
-
-
-
-
-
-
0.000 -
0.250
U, T
5.499
0.000 -
0.300
U, T
50.000
-
-
0 - 1
0
U, T
OFF
ON
Scaling
Data
Data
set
type
-
-
Float
-
-
Float
-
DDS
Float
-
DDS
Float
PERCEN
-
Float
T
-
DDS
U16
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Acc.
Level
3
3
3
3
2
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents