Function Commissioning; Overview Of Inverter Functions - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
P3900
End of quick commissioning
P1900
Select motor data identification
5.6

Function commissioning

5.6.1

Overview of inverter functions

The list below provides an overview of the main functions that the SINAMICS V20 supports.
For detailed description of individual parameters, see Chapter "Parameter list (Page 147)".
● 2/3 wire control (P0727)
● 50/60 Hz customization (Page 59) (P0100)
● Adjustable PWM modulation (P1800 to P1803)
● Analog input terminal function control (P0712, P0713, r0750 to P0762)
● Analog output terminal function control (P0773 to r0785)
● Automatic restart (Page 117) (P1210, P1211)
● BICO function (r3978)
● Blockage clearing mode (Page 111) (P3350 to P3353, P3361 to P3364)
● Cavitation protection (Page 125) (P2360 to P2362)
● Command and setpoint source selection (P0700, P0719, P1000 to r1025, P1070 to
r1084)
● Command data set (CDS) and inverter data set (DDS) (r0050, r0051, P0809 to P0821)
● Condensation protection (Page 119) (P3854)
● Continuous boost, acceleration boost and starting boost level control (Page 87) (P1310 to
P1316)
● DC coupling function (Page 128)
● DC-link voltage control (Page 104) (P0210, P1240 to P1257)
● Digital input terminal function control (P0701 to P0713, r0722, r0724)
● Digital output terminal function control (P0731, P0732, P0747, P0748)
● Dual ramp operation (Page 127) (r1119 to r1199, P2150 to P2166)
● Economy mode (Page 113) (P1300, r1348)
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Setting
= 0: No quick commissioning (factory default)
= 1: End quick commissioning with factory reset
= 2: End quick commissioning
= 3: End quick commissioning only for motor data
Note:
After completion of calculation, P3900 and P0010 are automati-
cally reset to their original value 0.
The inverter displays "8.8.8.8.8" which indicates that it is busy
with internal data processing.
= 0: Disabled
= 2: Identification of all parameters in standstill
Commissioning
5.6 Function commissioning
81

Hide quick links:

Advertisement

Table of Contents
loading