5.6.2.4

Setting the PID controller

Functionality
The integrated PID controller (technology controller) supports all kinds of simple process
control tasks, e.g. controlling pressures, levels, or flowrates. The PID controller specifies the
speed setpoint of the motor in such a way that the process variable to be controlled
corresponds to its setpoint.
Setting parameters
Parameter
Function
Main function parameters
P2200[0...2]
BI: Enable PID controller
P2235[0...2]
BI: Enable PID-MOP (UP-cmd)
P2236[0...2]
BI: Enable PID-MOP (DOWN-cmd)
Additional commissioning parameters
P2251
PID mode
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Setting
This parameter allows user to enable / disable the PID control-
ler. Setting to 1 enables the PID closed-loop controller.
Setting 1 automatically disables normal ramp times set in
P1120 and P1121 and the normal frequency setpoints.
Factory default: 0
This parameter defines source of UP command.
Possible sources: 19.13 (BOP), 722.x (Digital Input), 2036.13
(USS on RS485)
This parameter defines source of DOWN command.
Possible sources: 19.14 (BOP), 722.x (Digital Input), 2036.14
(USS on RS485)
= 0: PID as setpoint (factory default)
= 1: PID as trim source
Commissioning
5.6 Function commissioning
89