Faults and alarms
8.1 Faults
Fault
F350 (continued)
F395
Acceptance
test/confirmation pending
F410
Cavitation protection fail-
ure
F452
Load monitoring trip
288
Cause
r0949 = 13: Wrong power module
fitted.
r0949 > 1000: Internal failure -
wrong I/O board fitted.
This fault occurs after a startup clone. It
can also be caused by a faulty read
from the EEPROM, see F51 for more
details.
A startup clone could have changed
and might not match the application.
This parameter set needs to be
checked before the inverter can start a
motor.
r0949 = 3/4: Inverter data change
r0949 = 5: Startup clone via an
MMC/SD card has been performed
r0949 = 10: Previous startup clone
was aborted
Conditions exist for cavitation damage.
Cavitation damage is damage caused
to a pump in pumping systems when
the fluid is not flowing sufficiently. This
can lead to heat build up and subse-
quent damage to the pump.
Load conditions on motor indicate belt
failure or mechanical fault.
r0949 = 0: trip low torque / speed
r0949 = 1: trip high torque / speed
Remedy
The current parameter set needs to be checked and
confirmed by clearing the fault.
If cavitation is not occurring, reduce the cavitation
threshhold P2361, or increase the cavitation protec-
tion delay. Ensure sensor feedback is working.
Check the following:
No breakage, seizure or obstruction of inverter
train.
Apply lubrication if required.
If using an external speed sensor, check the follow-
ing parameters for correct function:
- P2192 (delay time for permitted deviation)
- P2182 (threshold frequency f1)
- P2183 (threshold frequency f2)
- P2184 (threshold frequency f3)
If using a specific torque / speed range, check pa-
rameters:
- P2182 (threshold frequency 1)
- P2183 (threshold frequency 2)
- P2184 (threshold frequency 3)
- P2185 (upper torque threshold 1)
- P2186 (lower torque threshold 1)
- P2187 (upper torque threshold 2)
- P2188 (lower torque threshold 2)
- P2189 (upper torque threshold 3)
- P2190 (lower torque threshold 3)
- P2192 (delay time for permitted deviation)
Operating Instructions, 09/2014, A5E34559884