Issue 10/06
2.3

Control terminals

Terminal
Designation
1
2
3
ADC1+
4
ADC1–
5
DIN1
6
DIN2
7
DIN3
8
DIN4
9
10
ADC2+
11
ADC2–
12
DAC1+
13
DAC1–
14
PTCA
15
PTCB
16
DIN5
17
DIN6
18
DOUT1/NC
19
DOUT1/NO
20
DOUT1/COM
21
DOUT2/NO
22
DOUT2/COM
23
DOUT3/NC
24
DOUT3/NO
25
DOUT3/COM
26
DAC2+
27
DAC2–
28
29
P+
30
N–
Fig. 2-9
Control terminals of MICROMASTER 440
MICROMASTER 440
Operating Instructions (Compact)
Function
Output +10 V
Output 0 V
Analog input 1 (+)
Analog input 1 (–)
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Isolated output +24 V / max. 100 mA
Analog input 2 (+)
Analog input 2 (–)
Analog output 1 (+)
Analog output 1 (–)
Connection for PTC / KTY84
Connection for PTC / KTY84
Digital input 5
Digital input 6
Digital output 1 / NC contact
Digital output 1 / NO contact
Digital output 1 / Changeover contact
Digital output 2 / NO contact
Digital output 2 / Changeover contact
Digital output 3 / NC contact
Digital output 3 / NO contact
Digital output 3 / Changeover contact
Analog output 2 (+)
Analog output 2 (–)
Isolated output 0 V / max. 100 mA
RS485 port
RS485 port