Setting The Automatic Restart Function - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

5.6.3.8

Setting the automatic restart function

Functionality
After a power failure (F3 "Undervoltage"), the automatic restart function (enabled using
P1210) automatically switches on the motor if an ON command is active. Any faults are
automatically acknowledged by the inverter.
When it comes to power failures (line supply failure), then a differentiation is made between
the following conditions:
● "Line undervoltage (mains brownout)" is a situation where the line supply is interrupted
and returns before the built-in BOP display has gone dark (this is an extremely short line
supply interruption where the DC link hasn't completely collapsed).
● "Line failure (mains blackout)" is a situation where the built-in BOP display has gone dark
(this represents a longer line supply interruption where the DC link has completely
collapsed) before the line supply returns.
Setting parameters
Parameter
Function
P1210
Automatic restart
P1211
Number of restart attempts
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Setting
This parameter configures automatic restart function.
= 0: Disabled
= 1: Trip reset after power on, P1211 disabled
= 2: Restart after mains blackout, P1211 disabled
= 3: Restart after mains brownout or fault, P1211 enabled
= 4: Restart after mains brownout, P1211 enabled
= 5: Restart after mains blackout and fault, P1211 disabled
= 6: Restart after mains brown / blackout or fault, P1211 ena-
bled
= 7: Restart after mains brown / blackout or fault, trip when
P1211 expires
This parameter specifies number of times inverter will attempt
to restart if automatic restart P1210 is activated.
Range: 0 to 10 (factory default: 3)
Commissioning
5.6 Function commissioning
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents