Siemens SINAMICS V20 Operating Instructions Manual page 253

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
Cavitation protection enabled.
Will generate a fault / warning when cavitation conditions are deemed to be present.
0
1
2
P2361[0...2]
Cavitation threshold [%]
Feedback threshold over which a fault / warning is triggered, as a percentage (%).
P2362[0...2]
Cavitation protection
time [s]
The time for which cavitation conditions have to be present before a fault / warning is triggered.
P2365[0...2]
Hibernation enable /
disable
Enable or disable the hibernation functionality.
0 = disabled
1 = enabled
P2366[0...2]
Delay before stopping
motor [s]
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
Can be
default
changed
Disable
Fault
Warn
0.00 -
40.00
U, T
200.00
0 - 65000
30
U, T
0 - 1
0
U, T
0 - 254
5
U, T
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
-
DDS
Float
-
DDS
U16
-
DDS
U16
-
DDS
U16
Acc.
Level
2
2
2
3
253