Setting Motor Data - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning
5.5.1.2

Setting motor data

Functionality
This menu is designed for easy setup of nominal motor nameplate data.
Text menu
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.
Setting parameters
Note
In the table below, "●" indicates that the value of this parameter must be entered according
to the rating plate of the motor.
Parameter
Access
level
P0100
1
P0304[0] ●
1
P0305[0] ●
1
P0307[0] ●
1
P0308[0] ●
1
P0309[0] ●
1
62
Function
50 / 60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
Rated motor voltage [V]
Note that the input of rating plate data must correspond with the wiring of
the motor (star / delta)
Rated motor current [A]
Note that the input of rating plate data must correspond with the wiring of
the motor (star / delta)
Rated motor power [kW / hp]
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
Rated motor power factor (cosφ)
Visible only when P0100 = 0 or 2
Rated motor efficiency [%]
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
Text menu
(if P8553 = 1)
(EU - US)
(MOT V)
(MOT A)
P0100 = 0 or 2:
(MOT P)
P0100 =1:
(MOT HP)
(M COS)
(M EFF)