Parameter
Function
03
04
05
P3852[0...2]
BI: Enable frost protec-
tion
Defines command source of protection enable command. If binary input is equal to one, then protection will
be initiated. If inverter is stopped and protection signal becomes active, protection measure is applied as
follows:
If P3853 ≠ 0, frost protection is applied by applying the given frequency to the motor
If P3853 = 0, and P3854 ≠ 0, condensation protection is applied by applying the given current to the
motor
Note:
The protection function may be overridden under the following circumstances:
If inverter is running and protection signal becomes active, signal is ignored
If inverter is turning motor due to active protection signal and a RUN command is received, RUN com-
mand overrides frost signal
Issuing an OFF command while protection is active will stop the motor
P3853[0...2]
Frost protection fre-
quency [Hz]
The frequency applied to the motor when frost protection is active.
Dependency: See also P3852.
P3854[0...2]
Condensation protec-
tion current [%]
The DC current (as a percentage of nominal current) which is applied to the motor when condensation
protection is active.
Dependency: See also P3852.
P3900
End of quick commis-
sioning
Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and
P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
0
1
2
3
Dependency: Changeable only when P0010 = 1 (quick commissioning).
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Super Torque Boost Off
Blockage Clearing Reverse On
Blockage Clearing Reverse Off
0 -
4294967295
0.00 -
550.00
0 - 250
0 - 3
No quick commissioning
End quick commissioning with factory reset
End quick commissioning
End quick commissioning only for motor data
Factory
Can be
default
changed
0
U, T
5.00
U, T
100
U, T
0
C(1)
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
Yes
No
Yes
No
Yes
No
-
CDS
U32
-
DDS
Float
-
DDS
U16
-
-
U16
Acc.
Level
2
2
2
1
277