Technical specifications
Electrical specifications
Line supply characteristics
Voltage range
Overvoltage category
Permissible supply
configuration
Supply environment
Note that only unfiltered variants can be operated on IT power system; to operate FSE filtered variant on IT power
1)
supply, make sure you remove the screw for the EMC filter.
Overload capability
Power rating (kW)
0.12 to 15
18.5 (HO)/22 (HO)
22 (LO)/30 (LO)
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Three phase AC 400 V inverters
380 V to 480 V AC (tolerance: -15% to +10%)
47 Hz to 63 Hz
Current derating at high input voltages:
Note: For the current derating at 480 V at the
default 4 kHz switching frequency and 40 °C
surrounding air temperature, refer to the table
in Section "Components of the inverter system
(Page 21)".
EN 60664-1 Category III
TN, TT, IT
, TT earthed line
1)
Second environment (private power network)
Average output
Overload current
current
100% rated
150% rated for 60
seconds
110% rated for 60
seconds
Single phase AC 230 V inverters
200 V to 240 V AC (tolerance: -10% to +10%)
47 Hz to 63 Hz
Current derating at high input voltages:
EN 60664-1 Category III
TN, TT
Second environment (private power network)
Maximum overload cycle
150% rated for 60 seconds followed by 94.5% rated for
240 seconds
110% rated for 60 seconds followed by more than 98%
rated for 240 seconds
A
293