Setting The Wobble Generator - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
P1080[0...2]
Minimum frequency [Hz]
5.6.3.12

Setting the wobble generator

Functionality
The wobble generator executes predefined periodical disruptions superimposed on the main
setpoint for technological usage in the fiber industry. The wobble function can be activated
via P2940. It is independent of the setpoint direction, thus only the absolute value of the
setpoint is relevant. The wobble signal is added to the main setpoint as an additional
setpoint. During the change of the setpoint the wobble function is inactive. The wobble signal
is also limited by the maximum frequency (P1082).
Setting parameters
Parameter
Function
P2940
BI: Release wobble function
P2945
Wobble signal frequency [Hz]
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Setting
Sets minimum motor frequency at which motor will run irre-
spective of frequency setpoint. Value set here is valid both for
clockwise and for anticlockwise rotation.
Range: 0.00 to 550.00 (factory default: 0.00)
Setting
This parameter defines the source to release the wobble func-
tion.
Factory default: 0.0
This parameter sets the frequency of the wobble signal.
Range: 0.001 to 10.000 (factory default: 1.000)
Commissioning
5.6 Function commissioning
121