Siemens SINAMICS V20 Operating Instructions Manual page 239

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
Dependency:
See P1175.
Note:
If P1175 is set, P2150 is also used to control the Dual Ramp function.
P2151[0...2]
CI: Speed setpoint for
messages
Selects the source of setpoint frequency, actual frequency is compared with this frequency to detect fre-
quency deviation (see monitoring bit r2197.7).
P2155[0...2]
Threshold frequency f_1
[Hz]
Sets a threshold for comparing actual speed or frequency to threshold values f_1. This threshold controls
status bits 4 and 5 in status word 2 (r0053).
P2156[0...2]
Delay time of threshold
freq f_1 [ms]
Sets delay time prior to threshold frequency f_1 comparison (P2155).
P2157[0...2]
Threshold frequency f_2
[Hz]
Threshold_2 for comparing speed or frequency to thresholds.
Dependency:
See P1175.
Note:
If P1175 is set, P2157 is also used to control the Dual Ramp function.
P2158[0...2]
Delay time of threshold
freq f_2 [ms]
When comparing speed or frequency to threshold f_2 (P2157) this is the time delay before status bits are
cleared.
P2159[0...2]
Threshold frequency f_3
[Hz]
Threshold_3 for comparing speed or frequency to thresholds.
Dependency:
See P1175.
Note:
If P1175 is set, P2159 is also used to control the Dual Ramp function.
P2160[0...2]
Delay time of threshold
freq f_3 [ms]
When comparing speed or frequency to threshold f_3 (P2159) this is the time delay before status bits are
set.
P2162[0...2]
Hysteresis freq. for over-
speed [Hz]
Hysteresis speed (frequency) for overspeed detection. For V/f control modes the hysteresis acts below the
maximum frequency.
P2164[0...2]
Hysteresis frequency
deviation [Hz]
Hysteresis frequency for detecting permitted deviation (from setpoint) or frequency or speed. This fre-
quency controls bit 8 in status word 1 (r0052).
P2166[0...2]
Delay time ramp up com-
pleted [ms]
Delay time for signal that indicates completion of ramp-up.
P2167[0...2]
Switch-off frequency f_off
[Hz]
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
Can be
default
changed
0 -
1170[0]
U, T
429496729
5
0.00 -
30.00
U, T
550.00
0 - 10000
10
U, T
0.00 -
30.00
U, T
550.00
0 - 10000
10
U, T
0.00 -
30.00
U, T
550.00
0 - 10000
10
U, T
0.00 - 25.00 3.00
U, T
0.00 - 10.00 3.00
U, T
0 - 10000
10
U, T
0.00 - 10.00 1.00
U, T
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
-
DDS
U32
-
DDS
Float
-
DDS
U16
-
DDS
Float
-
DDS
U16
-
DDS
Float
-
DDS
U16
-
DDS
Float
-
DDS
Float
-
DDS
U16
-
DDS
Float
Acc.
Level
3
3
3
2
2
2
2
3
3
3
3
239