Omron CS1G/H-CPUxxH Instructions Manual page 434

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxxH:
Table of Contents

Advertisement

Symbol Math Instructions
Description
Flags
Precautions
Examples
3-11-21 BCD MULTIPLY: *B(424)
Purpose
Ladder Symbol
Area
Index Registers
Indirect addressing
using Index Registers
*UL(423) multiplies the unsigned binary values in Md and Md+1 and Mr and
Mr+1 and outputs the result to R, R+1, R+2, and R+3.
Md + 1
×
Mr + 1
R + 3
R + 2
R + 1
Name
Label
Error Flag
ER
Equals Flag
=
Negative Flag
N
When *UL(423) is executed, the Error Flag will turn OFF.
If as a result of the multiplication, the content of R, R+1, R+2, R+3 is 0000
hex, the Equals Flag will turn ON.
If as a result of the multiplication, the content of the leftmost bit of R+3 is 1,
the Negative Flag will turn ON.
When CIO 000000 is ON in the following example, D00100, D00110, D00111,
and D00110 will be multiplied as 8-digit unsigned binary values and the result
will be output to D00123, D00122, D00121, and D00120.
Multiplies 4-digit (single-word) BCD data and/or constants.
Md
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
(Unsigned binary)
Md
(Unsigned binary)
Mr
R
(Unsigned binary)
Operation
OFF
ON when the result is 0.
OFF in all other cases.
ON when the leftmost bit of the result is 1.
OFF in all other cases.
*B(424)
Md
Md: Multiplicand word
Mr
Mr: Multiplier word
R
R: Result word
Section 3-11
Mr
R
413

Advertisement

Table of Contents
loading

Table of Contents