Interrupt Control Instructions
000000
CL1
N
S
3-20-4 DISABLE INTERRUPTS: DI(693)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
Description
760
15
14
D00100
1
1
0
D00100
F
0: Recorded interrupt input retained
1: Recorded interrupt input cleared
Example for C200HS-INT01
When CIO 000000 turns ON in the following example, CLI(691) clears the
recorded interrupts for interrupt inputs 3 and 6 in Interrupt Input Unit 2.
Example for Setting Time to First Scheduled Interrupt
When CIO 000000 turns ON in the following example, CLI(691) sets the time
to the first execution of scheduled interrupt 2 to 50 seconds.
(In this case, the scheduled time interval units are set to 10 ms in the PLC
Setup.)
Disables execution of all interrupt tasks except the power OFF interrupt.
When a CS1-H, CJ1-H, and CJ1M CPU Unit is being used and the power
OFF interrupt task is disabled, it is possible to disable power OFF interrupt
processing simultaneously.
DI(693)
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Block program areas
OK
DI(693) is executed from the main program to temporarily disable all interrupt
tasks except the power OFF interrupt (I/O interrupts, scheduled interrupts,
and external interrupts).
All interrupt tasks will be disabled until they are enabled again by execution of
EI(694).
13
12
11
10
9
8
7
6
1
1
0
1
0
1
1
1
5
Step program areas
OK
Section 3-20
5
4
3
2
1
0
1
1
0
0
1
0
F
2
DI(693)
@DI(693)
Not supported
Subroutines
Interrupt tasks
OK